Experimental and numerical investigation of the operating performance of air-to-air membrane enthalpy exchangers

被引:3
作者
Albdoor, Ahmed K. [1 ,2 ]
Ma, Zhenjun [1 ]
Al-Ghazzawi, Fatimah [2 ,3 ,4 ]
Liu, Jingjing [1 ]
Awan, Muhammed B. [1 ]
机构
[1] Univ Wollongong, Sustainable Bldg Res Ctr SBRC, Wollongong, NSW 2522, Australia
[2] Southern Tech Univ, Al Nasiriyah Tech Inst, Thi Qar 64001, Iraq
[3] Univ Wollongong, Intelligent Polymer Res Inst, Wollongong, NSW 2522, Australia
[4] Univ Wollongong, ARC Ctr Electromat Sci, Wollongong, NSW 2522, Australia
关键词
Energy recovery; Membrane enthalpy exchanger; Performance evaluation; Heat and moisture transfer; Mathematical modelling; MASS-TRANSFER; HEAT; PLATE; VENTILATION; SYSTEM;
D O I
10.1016/j.seta.2021.101722
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study examined the impacts of major operating parameters on the performance of a cross flow membrane enthalpy exchanger (MEE) with porous membranes. A lab-scale setup was developed to conduct the experiments based on the test matrix designed with various operating conditions for both heating and cooling operations. The MEE core was made of porous membranes. A mathematical model was developed to predict the transferred heat and moisture fluxes through the membrane. The model implemented a variable moisture diffusivity of the membrane that varied with local air conditions. It was found that the sensible, latent, and total effectiveness of the MEE significantly improved when reducing the airflow rate. In the cooling mode, outdoor air temperature and humidity had a positive influence on the MEE effectiveness, while they showed a negative impact on the heating operations. However, the influences of outdoor conditions on the sensible, latent, and total effectiveness of the MEE were rather insignificant as compared to that of the airflow rate. On the other hand, both airflow rate and outdoor conditions showed significant effects on thermal resistance and total energy recovered for both operating modes. The findings obtained can be used to facilitate optimal design of such devices.
引用
收藏
页数:11
相关论文
共 41 条
[11]   Indirect evaporative cooling: Past, present and future potentials [J].
Duan, Zhiyin ;
Zhan, Changhong ;
Zhang, Xingxing ;
Mustafa, Mahmud ;
Zhao, Xudong ;
Alimohammadisagvand, Behrang ;
Hasan, Ala .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2012, 16 (09) :6823-6850
[12]   Heat and mass transfer modeling in enthalpy exchangers using asymmetric composite membranes [J].
Engarnevis, Amin ;
Huizing, Ryan ;
Green, Sheldon ;
Rogak, Steven .
JOURNAL OF MEMBRANE SCIENCE, 2018, 556 :248-262
[13]   Material properties and measurements for semi-permeable membranes used in energy exchangers [J].
Ge, Gaoming ;
Mahmood, Gazi I. ;
Moghaddam, Davood Ghadiri ;
Simonson, Carey J. ;
Besant, Robert W. ;
Hanson, Stephen ;
Erb, Blake ;
Gibson, Phillip W. .
JOURNAL OF MEMBRANE SCIENCE, 2014, 453 :328-336
[14]   Energy performance comparison of three innovative HVAC systems for renovation through dynamic simulation [J].
Gustafsson, Marcus ;
Dermentzis, Georgios ;
Myhren, Jonn Are ;
Bales, Chris ;
Ochs, Fabian ;
Holmberg, Sture ;
Feist, Wolfgang .
ENERGY AND BUILDINGS, 2014, 82 :512-519
[15]   Investigation of Ventilation Energy Recovery with Polymer Membrane Material-Based Counter-Flow Energy Exchanger for Nearly Zero-Energy Buildings [J].
Kassai, Miklos ;
Al-Hyari, Laith .
ENERGIES, 2019, 12 (09)
[16]   Membrane modules for building ventilation [J].
Kistler, KR ;
Cussler, EL .
CHEMICAL ENGINEERING RESEARCH & DESIGN, 2002, 80 (A1) :53-64
[17]   Development and evaluation of a ceiling ventilation system enhanced by solar photovoltaic thermal collectors and phase change materials [J].
Lin, Wenye ;
Ma, Zhenjun ;
Sohel, M. Imroz ;
Cooper, Paul .
ENERGY CONVERSION AND MANAGEMENT, 2014, 88 :218-230
[18]   Direct contact membrane distillation for liquid desiccant regeneration and fresh water production: Experimental investigation, response surface modeling and optimization [J].
Liu, Jingjing ;
Ren, Haoshan ;
Hai, Faisal, I ;
Albdoor, Ahmed K. ;
Ma, Zhenjun .
APPLIED THERMAL ENGINEERING, 2021, 184
[19]   Performance of a quasi-counter-flow air-to-air membrane energy exchanger in cold climates [J].
Liu, Peng ;
Alonso, Maria Justo ;
Mathisen, Hans Martin ;
Simonson, Carey .
ENERGY AND BUILDINGS, 2016, 119 :129-142
[20]   A theoretical model to predict frosting limits in cross-flow air-to-air flat plate heat/energy exchangers [J].
Liu, Peng ;
Nasr, Mohammad Rafati ;
Ge, Gaoming ;
Alonso, Maria Justo ;
Mathisen, Hans Martin ;
Fathieh, Farhad ;
Simonson, Carey .
ENERGY AND BUILDINGS, 2016, 110 :404-414