Evaluation of Indoor Air Quality in Classrooms Equipped with Cross-Flow Ventilation

被引:0
作者
Conceicao, Eusebio Z. E. [1 ]
Farinho, Joao P. [1 ]
Lucio, Ma Manuela J. R. [1 ]
机构
[1] Univ Algarve, Fac Sci & Technol, P-8005139 Faro, Portugal
关键词
air quality; experimental and numerical method; tracer gas; cross flow ventilation; classrooms; air renovation rate; airflow rate; school; EFFICIENCY;
D O I
10.1080/14733315.2012.11683970
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this work the evaluation of indoor air quality in a classroom equipped with cross-flow ventilation is presented. A numerical methodology, based on comparison with experimental data, used in the evaluation of the air exchange rate, airflow rate and the age of the air, was applied in the first phase of this work. The evolution of carbon dioxide inside spaces, with different airflow typologies, was then predicted in the second part. The study was based on a school located in the South of Portugal. In the experimental methodology the tracer gas decay method was applied. In order to reduce the experimental time, the first minutes of the test were measured, while the remaining decay was obtained using a numerical exponential regression. Natural and forced cross-flow ventilation topologies were analyzed. In the case of forced ventilation, fresh air from the external environment was driven into the classroom through an air inlet using a supply fan. An extract strategy was also used in which stale air was mechanically extracted from the classroom. Natural ventilation consisted of opening perimeter and above-door windows. The forecast of carbon dioxide evolution was made using software that evaluates the thermal response of and air quality in a building with complex topology. The numerical model used to evaluate internal air quality was based on energy and mass conservation integral equations. These were solved using the Runge-Kutta-Fehlberg method with error control.
引用
收藏
页码:53 / 67
页数:15
相关论文
共 20 条
[1]  
[Anonymous], 2004, P 9 C AIR DISTR ROOM
[2]  
[Anonymous], 2006, DIARIO REPUBL A 0404
[3]  
[ANSI ASHRAE], 2004, 621 ANSIASHRAE
[4]  
Breum NO, 1992, ROOMVENT 92 AIR DIST, V3
[5]  
Breum NO, 1991, BUILD SERV ENGTECHN, V12, P39
[6]  
Breum NO, 1988, P 2 INT S VENT CONT, P373
[7]   Numerical Study of the Influence of Opaque External Trees with Pyramidal Shape on the Thermal Behaviour of a School Building in Summer Conditions [J].
Conceicao, Eusebio Z. E. ;
Lucio, M. Manuela J. R. .
INDOOR AND BUILT ENVIRONMENT, 2010, 19 (06) :657-667
[8]  
Conceiçao EZE, 2008, INT J VENT, V7, P267
[9]   Numerical Study of the Thermal Efficiency of a School Building with Complex Topology for Different Orientations [J].
Conceicao, Eusebio Z. E. ;
Lucio, Ma Manuela J. R. .
INDOOR AND BUILT ENVIRONMENT, 2009, 18 (01) :41-51
[10]  
Conceicao EZE, 2006, P HLTH BUILD 2006 LI, V3, P195