EDeSSOpt - Energy Demand and Supply Simultaneous Optimization for cost-optimized design: Application to a multi-family building

被引:36
作者
Ferrara, Maria [1 ]
Rolfo, Andrea [1 ]
Prunotto, Federico [1 ]
Fabrizio, Enrico [1 ,2 ]
机构
[1] Politecn Torino, DENERG, Corso Duca Abruzzi 24, I-10129 Turin, Italy
[2] FULL, Via Agostino da Montefeltro 2, I-10134 Turin, Italy
关键词
Simulation-based optimization; Integrated optimization; Social housing; EPBD second recast 2018; Global cost; Nearly zero energy buildings; MULTIOBJECTIVE OPTIMIZATION; MULTISTAGE OPTIMIZATION; RESIDENTIAL BUILDINGS; OFFICE BUILDINGS; MODEL; SYSTEM; VENTILATION; REDUCTION; OPERATION; COMFORT;
D O I
10.1016/j.apenergy.2018.12.043
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In the context of European efforts to reduce energy consumption and CO2 emissions in the building sector, the second recast of the Energy Performance of Buildings Directive promotes the acceleration of the energy renovation of European building stock. To do this, a cost optimization is necessary to find the best combination of energy efficiency measures which minimize the global cost during the entire life-cycle of the building, as suggested in the first recast of the same Directive. Since a great number of combinations must be analyzed, an automated procedure is necessary to reduce the calculation time. In this work, an iterative input-output process is set, thanks to the coupling of a dynamic energy simulation software (TRNSYS) and a generic optimization software (GenOpt). The cost optimization is applied to a new social housing construction - a multi-family building located in Northern Italy. The methodology that was adopted allows the simultaneous optimization of both the building energy demand (building envelope) and the building energy supply (technical systems and renewable sources). Results are compared with those obtained using a more widespread sequential approach whose purpose is firstly the optimization of one of these two factors, and subsequently the optimization of the other one. This study has demonstrated that an integrated approach allows a larger number of possible combinations of energy efficiency measures to be explored with respect to the sequential approach.
引用
收藏
页码:1231 / 1248
页数:18
相关论文
共 50 条
[1]   Cost-optimal thermal energy storage system for a residential building with heat pump heating and demand response control [J].
Alimohammadisagvand, Behrang ;
Jokisalo, Juha ;
Kilpelainen, Simo ;
Ali, Mubbashir ;
Siren, Kai .
APPLIED ENERGY, 2016, 174 :275-287
[2]   A review on simulation-based optimization methods applied to building performance analysis [J].
Anh-Tuan Nguyen ;
Reiter, Sigrid ;
Rigo, Philippe .
APPLIED ENERGY, 2014, 113 :1043-1058
[3]  
[Anonymous], 2017, LISTINO PREZZI ESECU
[4]  
[Anonymous], 2013, U WUPP NEARL ZER EN
[5]  
[Anonymous], 151931 UNI EN
[6]  
[Anonymous], 2014, 113002 UNI TS
[7]  
[Anonymous], 2007, 15459 EN
[8]   Earth-to-air heat exchanger for NZEB in Mediterranean climate [J].
Ascione, Fabrizio ;
D'Agostino, Diana ;
Marino, Concetta ;
Minichiello, Francesco .
RENEWABLE ENERGY, 2016, 99 :553-563
[9]   Multi-objective optimization of the renewable energy mix for a building [J].
Ascione, Fabrizio ;
Bianco, Nicola ;
De Masi, Rosa Francesca ;
De Stasio, Claudio ;
Mauro, Gerardo Maria ;
Vanoli, Giuseppe Peter .
APPLIED THERMAL ENGINEERING, 2016, 101 :612-621
[10]   Multi-stage and multi-objective optimization for energy retrofitting a developed hospital reference building: A new approach to assess cost-optimality [J].
Ascione, Fabrizio ;
Bianco, Nicola ;
De Stasio, Claudio ;
Mauro, Gerardo Maria ;
Vanoli, Giuseppe Peter .