Partial Discharge Localization Using Electromagnetic Time Reversal: A Performance Analysis

被引:18
作者
Azadifar, Mohammad [1 ]
Karami, Hamidreza [2 ,3 ]
Wang, Zhaoyang [2 ]
Rubinstein, Marcos [1 ]
Rachidi, Farhad [2 ]
Karami, Hossein [4 ]
Ghasemi, Ali [5 ]
Gharehpetian, Gevork B. [6 ]
机构
[1] Univ Appl Sci Western Switzerland HES SO, Inst Informat & Commun Technol IICT, CH-1401 Yverdon, Switzerland
[2] Swiss Fed Inst Technol EPFL, Electromagnet Compatibil Lab, CH-1015 Lausanne, Switzerland
[3] Bu Ali Sina Univ, Dept Elect Engn, Hamadan 65178, Hamadan, Iran
[4] Niroo Res Inst, High Voltage Res Grp, Tehran 1996836111, Iran
[5] Shahed Univ, Dept Elect Engn, Tehran 3319118651, Iran
[6] Amirkabir Univ Technol, Dept Elect Engn, Tehran Polytech, Tehran 15914, Iran
关键词
Experimental analysis; partial discharge localization; time difference of arrival; electromagnetic time reversal process; transformer tank; POWER TRANSFORMERS; LOCATION;
D O I
10.1109/ACCESS.2020.3015973
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In this study, first, a comparison on the application of electromagnetic time reversal (EMTR) and time difference of arrival (TDoA) in partial discharge localization in power transformers is presented. A two-dimensional finite-difference time-domain simulation is used to calculate the signal recorded by the sensors. Results show that, in a transformer tank excluding its windings, both methods yield similar results in terms of location accuracy, although the EMTR method only needs one sensor to localize the partial discharge (PD) source while the TDoA method needs at least three sensors in the 2D localization problem. However, the presence of transformer windings leads to a degradation of the performance of the TDoA method if the line of sight from the source to the sensor is blocked by any of the winding blocks. On the other hand, the presence of the transformer windings has an effect on the localization of PD sources that occur between two adjacent phase windings when the distance between the outer winding distances is shorter than the minimum wavelength, lambda(min). The degradation is directly caused by the diffraction limit. It is shown that, if the distance between two adjacent phase windings is greater than lambda(min), the EMTR process can locate PD sources occurring between two adjacent phase windings with acceptable accuracy. A case of occurrence of PDs in close proximity (less than lambda(min)/2) to a single metallic object is analyzed both numerically and experimentally. The analysis reveals that although a degradation in the accuracy of the localization is observed compared to the case of longer distances between the PD source and the metallic object, a reasonable localization error of 10 mm (corresponding to lambda(min)/10) is obtained.
引用
收藏
页码:147507 / 147515
页数:9
相关论文
共 27 条
  • [1] On the Use of Monopole Antennas for Determining the Effect of the Enclosure of a Power Transformer Tank in Partial Discharges Electromagnetic Propagation
    Albarracin, Ricardo
    Alfredo Ardila-Rey, Jorge
    Mas'ud, Abdullahi Abubakar
    [J]. SENSORS, 2016, 16 (02):
  • [2] Ali NHN, 2016, 2016 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), P519, DOI 10.1109/EIC.2016.7548651
  • [3] [Anonymous], 2017, WD129 CIGRE
  • [4] [Anonymous], 1993, J PHYS D APPL PHYS
  • [5] Theory of the time reversal cavity for electromagnetic fields
    Carminati, R.
    Pierrat, R.
    de Rosny, J.
    Fink, M.
    [J]. OPTICS LETTERS, 2007, 32 (21) : 3107 - 3109
  • [6] Taking advantage of multiple scattering to communicate with time-reversal antennas
    Derode, A
    Tourin, A
    de Rosny, J
    Tanter, M
    Yon, S
    Fink, M
    [J]. PHYSICAL REVIEW LETTERS, 2003, 90 (01) : 014301/1 - 014301/4
  • [7] Du JC, 2016, C ELECT INSUL DIEL P, P179, DOI 10.1109/CEIDP.2016.7785485
  • [8] A review of faults detectable by gas-in-oil analysis in transformers
    Duval, M
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (03) : 8 - 17
  • [9] Time reversed acoustics
    Fink, M
    [J]. PHYSICS TODAY, 1997, 50 (03) : 34 - 40
  • [10] Partial discharge monitoring for power transformers using UHF sensors - part 2: Field experience
    Judd, MD
    Yang, L
    Hunter, IBB
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2005, 21 (03) : 5 - 13