Limiting characteristics of the superconducting fault current limiter applied to the neutral line of conventional transformer

被引:3
作者
Im, I. G. [1 ]
Choi, H. S. [1 ]
Jung, B. I. [1 ]
机构
[1] Chosun Univ, Dept Elect Engn, Kwangju 501759, South Korea
来源
PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS | 2013年 / 494卷
关键词
Transformer; Superconducting; Fault current limiter; Quench;
D O I
10.1016/j.physc.2013.04.082
中图分类号
O59 [应用物理学];
学科分类号
摘要
The increased electricity demands influenced by the recent industrial development make the electric power distribution system more comprehensive, and the risks are high to cause failures to steady state electric line due to the extended range of fault at the time of fault occurrence. Also, the high performance and the high precision electric appliances that sensitive to switching surge and fault current expose vulnerability of reduced life span and increased fault occurrence ratio. Therefore, this thesis analyzed the fault limiting characteristics by the fault types by applying the superconducting fault current limiter to the neutral line of the transformer in order to reduce the fault currents that flow such high performance appliances. A current transformer (CT) that detects the fault current in the simulated power distribution system, a switching control system that is self-developed and a transformer are used in constructing a circuit. When a fault occurs, the initial fault current is restricted by the superconducting fault current limiter and simultaneously detours the fault current by operating the SCR contact of the switching control system through the detection by CT. This thesis analyzed the limiting characteristics of the superconducting fault current limiter that are applied to the neutral line of the transformer by the fault types. (C) 2013 Elsevier B.V. All rights reserved.
引用
收藏
页码:339 / 343
页数:5
相关论文
共 7 条
[1]   Operational characteristics in the three-phase transformer-type SFCL with neutral line based on sequential reclosing process [J].
Cho, Y. S. ;
Choi, H. S. ;
Jung, B. I. .
PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2011, 471 (21-22) :1341-1347
[2]  
Cho Y.S., 2006, T KOREAN I ELECT E A, V55A, P62
[3]  
Choi Hyo-Sang, 2010, [THE TRANSACTIONS OF THE KOREAN INSTITUTE OF ELECTRICAL ENGINEERS : P, 전기학회 논문지 P권], V59, P330
[4]   Transient Characteristics of a Flux-Coupling Type Superconducting Fault Current Limiter According to Winding Direction [J].
Choi, Hyo-Sang ;
Jung, Byung-Ik ;
Cho, Yong-Sung .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2009, 19 (03) :1827-1830
[5]   Study on Superconducting Fault Current Limiters Based on Normal Transformers [J].
Chung, Dong Chul ;
Pak, Byeong Ha ;
Cho, Yong Sun ;
Jung, Byung Ik ;
Sung, Tae Hyn ;
Choi, Hyo Sang .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2012, 22 (03)
[6]   Testing bulk HTS modules for resistive superconducting fault current limiters [J].
Noe, M ;
Juengst, KP ;
Werfel, FN ;
Elschner, S ;
Bock, J ;
Breuer, F ;
Kreutz, R .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2003, 13 (02) :1976-1979
[7]   Study on Protection Coordination Between Protective Devices in a Power Distribution System With an SFCL [J].
You, Il-Kyoung ;
Lim, Sung-Hun ;
Kim, Jae-Chul ;
Hyun, Ok-Bae .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2010, 20 (03) :1168-1171