A Fault Detection Technique for the Series-Compensated Line During Power Swing

被引:109
作者
Nayak, Paresh Kumar [1 ]
Pradhan, Ashok Kumar [1 ]
Bajpai, Prabodh [1 ]
机构
[1] Indian Inst Technol, Dept Elect Engn, Kharagpur 721302, W Bengal, India
关键词
Digital relaying; distance protection; fault detection; power swing; series compensation; DISTANCE RELAY; PROTECTION; SCHEME;
D O I
10.1109/TPWRD.2012.2231886
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A distance relaying scheme is susceptible to power swing. To avoid unintended trip operation during such conditions, a power swing blocking function is utilized in distance relays. However, if a fault occurs during power swing, the relay should detect the fault and trip as soon as possible. The detection of fault in a series-compensated line during the power swing is further complicated due to complex transients produced by series capacitor and the metal-oxide varistor (MOV) protecting it. This paper proposes a negative-sequence current-based technique for detecting all types of faults during the power swing in a series-compensated line. The technique is tested for different series-compensated systems including a 9-bus 3-machine power system. Different types of faults: symmetrical, asymmetrical, and high resistance occurring during the power swing are simulated through EMTDC/PSCAD to test the algorithm. The method is compared with available techniques and found to be accurate and fast.
引用
收藏
页码:714 / 722
页数:9
相关论文
共 21 条
[1]   Modem approaches for protection of series compensated transmission lines [J].
Abdelaziz, AY ;
Ibrahim, AM ;
Mansour, MM ;
Talaat, HE .
ELECTRIC POWER SYSTEMS RESEARCH, 2005, 75 (01) :85-98
[2]  
Alture H.J., 2008, ADV SERIES COMPENSAT, VTP6340-01, P1
[3]  
Apostolov AP, 2004, 2004 IEEE PES POWER SYSTEMS CONFERENCE & EXPOSITION, VOLS 1 - 3, P592
[4]  
Benmouyal G., 2004, P 31 ANN W PROT REL
[5]   Distance relay with out-of-step-blocking function using wavelet transform [J].
Brahma, Sukumar M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (03) :1360-1366
[6]  
Esmaeilian Ghaderi A, 2011, P 10 INT C ENV EL EN, P1842
[7]  
Gao Z. D., 1991, APSCOM-91. 1991 International Conference on Advances in Power System Control, Operation and Management (Conf. Publ. No.348), P843
[8]  
Gustafsson F., 2000, Adaptive filtering and change detection
[9]  
IEEE Power System Relaying Committee of the IEEE Power Eng. Soc, 2005, D6 PSRC WG IEEE POW
[10]   A novel scheme to identify symmetrical faults occurring during power swings [J].
Lin, Xiangning ;
Gao, Yan ;
Liu, Pei .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (01) :73-78