High-Sensitivity Fiber-Optic Sensor for Hydrogen Detection in Gas and Transformer Oil

被引:33
作者
Fisser, Maximilian [1 ]
Badcock, Rodney A. [1 ]
Teal, Paul D. [2 ]
Hunze, Arvid [1 ]
机构
[1] Victoria Univ Wellington, Robinson Res Inst, Lower Hutt 5046, New Zealand
[2] Victoria Univ Wellington, Sch Engn & Comp Sci, Wellington 6104, New Zealand
关键词
Fiber Bragg grating; gas detection; hydrogen; palladium; transformer monitoring; PALLADIUM; ABSORPTION; CO; PD; PERMEATION;
D O I
10.1109/JSEN.2019.2891523
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper reports on the characterization of a palladium (Pd)-based fiber-optic hydrogen (H-2) sensor for health monitoring of distribution and power transformers in the electrical grid. The sensor consists of a Pd foil, which expands due to H-2 absorption, and a fiber Bragg grating that measures this expansion. Fifteen sensors were manufactured and characterized in gas and oil environments at various H-2 concentrations and temperatures. In gas, the sensors were evaluated at 60 degrees C, 75 degrees C, 90 degrees C, 105 degrees C, and 120 degrees C and H-2 concentrations from 0.01% to 5%. In oil, the same sensors were evaluated at 90 degrees C and dissolved H-2 concentrations from S to 2700 ppm. Furthermore, the influence of carbon monoxide (CO), which is often present in transformers and can impact H-2 response of the sensor, was investigated. At 90 degrees C in gas, the response to 0.01% and 5% H-2 was on average 28 and 719 pm, respectively. At 90 degrees C in oil, the response to S and 2700 ppm dissolved H-2 was on average 11 and 763 pm, respectively. The average, relative accuracy is better than 20% over the whole measurement range in gas and for measurements above 100 ppm in oil. These specifications make the sensor a promising candidate for online monitoring of H-2 in transformers.
引用
收藏
页码:3348 / 3357
页数:10
相关论文
共 33 条
[1]   The role of palladium in a hydrogen economy [J].
Adams, Brian D. ;
Chen, Aicheng .
MATERIALS TODAY, 2011, 14 (06) :282-289
[2]  
Alefeld G., 1978, Hydrogen in Metals II: Application-Oriented Properties, V29
[3]  
Alefeld G., 1978, HYDROGEN METALS I BA, V28, P442
[4]   Hydrogen permeation through surface modified Pd and PdAg membranes [J].
Amandusson, H ;
Ekedahl, LG ;
Dannetun, H .
JOURNAL OF MEMBRANE SCIENCE, 2001, 193 (01) :35-47
[5]   EFFECTS OF HIGH-CONCENTRATION CO AND CO2 ON HYDROGEN PERMEATION THROUGH THE PALLADIUM MEMBRANE [J].
AMANO, M ;
NISHIMURA, C ;
KOMAKI, M .
MATERIALS TRANSACTIONS JIM, 1990, 31 (05) :404-408
[6]  
[Anonymous], 2008, C57104 IEEE
[7]  
[Anonymous], P SPIE
[8]   Optical fiber sensors for static and dynamic health monitoring of civil engineering infrastructures: Abode wall case study [J].
Antunes, Paulo ;
Lima, Hugo ;
Varum, Humberto ;
Andre, Paulo .
MEASUREMENT, 2012, 45 (07) :1695-1705
[9]  
AUER W, 1974, BER BUNSEN PHYS CHEM, V78, P58
[10]   THE INFLUENCE OF CARBON-MONOXIDE ON HYDROGEN ABSORPTION BY THIN-FILMS OF PALLADIUM [J].
CZERWINSKI, A ;
ZAMPONI, S ;
MARASSI, R .
JOURNAL OF ELECTROANALYTICAL CHEMISTRY, 1991, 304 (1-2) :233-239