Analysis of a new method of measurement and visualization of indoor conditions by infrared thermography

被引:8
作者
Djupkep, F. B. D. [1 ]
Maldague, X. [1 ]
Bendada, A. [1 ]
Bison, P. [2 ]
机构
[1] Univ Laval, Comp Vis & Syst Lab, Quebec City, PQ G1V 0A6, Canada
[2] CNR ITC, I-35127 Padua, Italy
基金
加拿大自然科学与工程研究理事会;
关键词
Heat transfer - Thermography (imaging) - Atmospheric temperature - Inverse problems - Parameter estimation - Three dimensional computer graphics - Thermography (temperature measurement);
D O I
10.1063/1.4818919
中图分类号
TH7 [仪器、仪表];
学科分类号
0804 ; 080401 ; 081102 ;
摘要
We present a new tool of measurement and visualization of the indoor ambient parameters (air temperature, air speed, and mean radiant temperature) by infrared thermography. The theoretical fundamentals are discussed. They include a design stage, the mathematical modeling, the measurement procedure, and the performance evaluation through error analysis. The measuring system consists of a set of auxiliary devices (targets) arranged on a measurement grid. An infrared camera measures their temperature histories. From each temperature chronology, the three ambient parameters are locally deduced together by solving an inverse heat transfer problem. The results are then mapped to provide a 2D or 3D visualization. The question of identifiability is addressed leading to a robust parameter estimation algorithm. The robustness of the algorithm is tested for a wide range of noisy data during a numerical experiment. The numerical data are built by varying the air speed from 0 ms(-1) to 2 ms(-1) with a step of 0.2 ms(-1), the air temperature from 15 degrees C to 30 degrees C with a step of 3 degrees C and the mean radiant temperature from 15 degrees C to 30 degrees C with a step of 3 degrees C. It appears that stability and repeatability are guaranteed by the presented method for the range of ambient parameters and accuracy usually found and needed in indoor conditions. Brief illustrative experimental results are given as an initial validation of the method. Since the spatial distributions of these ambient parameters are obtained qualitatively and quantitatively, the method is suitable for indoor microclimate mapping, visualization of air patterns, building inspection, thermal comfort assessment, etc. (C) 2013 AIP Publishing LLC.
引用
收藏
页数:11
相关论文
共 18 条
[1]  
[Anonymous], 2002, 7726 ISO
[2]  
[Anonymous], 2010, 552010 ANSIASHRAE
[3]  
ASHRAE, 2001, ASHRAE FUND HDB
[4]  
Beck J.V., 1977, Parameter estimation in engineering and science
[5]   Measurements of air temperatures close to a low-velocity diffuser in displacement ventilation using an infrared camera [J].
Cehlin, M ;
Moshfegh, B ;
Sandberg, M .
ENERGY AND BUILDINGS, 2002, 34 (07) :687-698
[6]   LAY EPIDEMIOLOGY AND THE PREVENTION PARADOX - THE IMPLICATIONS OF CORONARY CANDIDACY FOR HEALTH-EDUCATION [J].
DAVISON, C ;
SMITH, GD ;
FRANKEL, S .
SOCIOLOGY OF HEALTH & ILLNESS, 1991, 13 (01) :1-19
[7]  
Djupkep F. B. D., 2011, P AITA 2011 ATT FOND, P31
[8]  
Fanger PO, 1973, THERMAL COMFORT
[9]  
Incropera F.P., 2007, FUNDAMENTAL HEAT MAS, P256
[10]  
Khuen L. A., 1970, J APPL PHYSIOL, V29, P750