Evaluation of Differential Pressure Setpoint of Chilled Water Pumps in Clean Room HVAC Systems for Energy Savings in High-Tech Industries

被引:20
作者
Su, Chun-Lien [1 ]
Yu, Kuen-Tyng [2 ]
机构
[1] Natl Kaohsiung Marine Univ, Dept Marine Engn, Kaohsiung 81157, Taiwan
[2] Orient Semicond Elect Ltd, Gen Adm Grp, Facil Dept, Kaohsiung 81157, Taiwan
关键词
Chilled water pumps; clean room; differential pressure; energy savings; field testing; high-tech industries; GLOBAL OPTIMIZATION;
D O I
10.1109/TIA.2013.2251992
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Variable-frequency speed control technologies are widely used in chilled water pumps in clean room heating, ventilation, and air-conditioning (HVAC) systems in high-tech industries to reduce energy consumption. Pumps with variable frequency drivers work based on the reading from the differential pressure sensor placed between the chilled water supply and return lines before the secondary and tertiary pumps. The determination of the differential pressure setpoint must take pipeline topology and material, chilled water flow demand, heat loading, and system equipment aging into account so as to provide operating flexibility for energy conservation while ensuring the secure operation of the clean room. To enhance clean room energy efficiency, a new methodology is proposed in this paper for determining the proper chilled piping pressure setpoint for the pumps. The mathematic model of head loss required for generic secondary and tertiary chilled networks widely used in clean rooms is derived using the Hazen-Williams formula principle. The field testing results confirm the validity of the proposed approach through a practical clean room HVAC system for electronic semiconductor manufacturing, and the energy savings and investment benefits due to the use of the proper differential pressure setpoint are determined.
引用
收藏
页码:1015 / 1022
页数:8
相关论文
共 11 条
  • [1] Brater E.F., 1996, HDB HYDRAULICS, V7th
  • [2] Chilled Water Secondary Pumps LONIX Ltd., CHILL WAT SEC PUMPS
  • [3] Energy evaluation of optimal control strategies for central VWV chiller systems
    Jin, Xinqiao
    Du, Zhimin
    Xiao, Xiaokun
    [J]. APPLIED THERMAL ENGINEERING, 2007, 27 (5-6) : 934 - 941
  • [4] Lee S.-K., 2009, J. Sci. Eng. Technol, V5, P57
  • [5] Liu GP, 2007, ASHRAE TRAN, V113, P362
  • [6] Global optimization for overall HVAC systems - Part I problem formulation and analysis
    Lu, L
    Cai, WJ
    Chai, YS
    Xie, LH
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2005, 46 (7-8) : 999 - 1014
  • [7] Global optimization for overall HVAC systems - Part II problem solution and simulations
    Lu, L
    Cai, WJ
    Soh, YC
    Xie, LH
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2005, 46 (7-8) : 1015 - 1028
  • [8] Moore B.J., 2003, ASHRAE Transactions, V109, P373
  • [9] Pitt R., 2008, COMP PIPE FLOW FORMU
  • [10] The Status of the Semiconductor Industry in Taiwan Taiwan Semiconductor Ind. Assoc. (TSIA), STAT SEM IND TAIW