摘要
To operate power transformers long-term, as well as ensuring their insulating reliability, adequate consideration must also be paid to the age-related decline in various insulating oil characteristics. This decline is considered attributable to the generation and increase of trace components in oil over time, which were not present when the oil was new. In this paper, to identify the components causing such degradation, various components detected in actual field aged transformers were added to the base oil to measure a range of characteristics (water content, acidity, interfacial tension, breakdown voltage, dissipation factor, and volume resistivity). The influence of these additives on various characteristics of insulating oil was evaluated to investigate the components responsible for the decline. When organic acids were added, the acidity value declined, as well as a significant decline in volume resistivity for decanoic acid among organic acids. For methyl ethyl ketone, which is a kind of ketones, a degradation of the characteristics was observed in the dissipation factor and volume resistivity, showing the same trend as that in the investigation results of the actual transformer oil. It emerged that phthalate compounds, or those derived from rubber material among the aromatic series, influenced the dissipation factor and volume resistivity in the presence of water. Consequently, the influence of various components detected in actual transformer oil on various characteristics of insulating oil was clarified.
引用
收藏
页码:2216 / 2224
页数:9
相关论文
共 50 条
  • [41] Design and fabrication of the degradation level monitoring sensor for power transformer insulating oil - art. no. 61110U
    Kim, Sunghyun
    Kim, Yiseok
    Yang, Jooran
    Kwon, Sangjin
    Park, Sekwang
    Reliability, Packaging, Testing, and Characterization of MEMS/ MOEMS V, 2006, 6111 : U1110 - U1110
  • [42] Amorphous graphene - Transformer oil nanofluids with superior thermal and insulating properties
    Bhunia, Mississippi Missouri
    Panigrahi, Karamjyoti
    Das, Swati
    Chattopadhyay, Kalyan Kumar
    Chattopadhyay, Paramita
    CARBON, 2018, 139 : 1010 - 1019
  • [43] Influence of Various Compounds on Electrostatic Charging Tendency in Insulating Oil
    Okabe, Sigemitsu
    Kotoh, Masanori
    Tsuchie, Motoo
    Amimoto, Tsuyoshi
    ELECTRICAL ENGINEERING IN JAPAN, 2011, 176 (03) : 29 - 36
  • [44] Degradation Assessment of In-Service Transformer Oil Based on Electrical and Chemical Properties
    Mustafa, Ehtasham
    Ahmad, Bilal
    Ali, Malik Imran
    Afia, Ramy S. A.
    Ullah, Rahmat
    APPLIED SCIENCES-BASEL, 2024, 14 (24):
  • [45] Partial Discharge-induced Degradation Characteristics of Oil-impregnated Insulating Material Used in Oil-immersed Power Transformers
    Okabe, Shigemitsu
    Ueta, Genyo
    Wada, Haruhisa
    Okubo, Hitoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (04) : 1225 - 1233
  • [46] Partial Discharge-induced Degradation Characteristics of Insulating Structure Constituting Oil-immersed Power Transformers
    Okabe, Shigemitsu
    Ueta, Genyo
    Wada, Haruhisa
    Okubo, Hitoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (05) : 1649 - 1656
  • [47] Investigations of thermal degradation and spectral response of transformer oil
    Radha, Karthik
    Thangaswamy, Renga Raja
    ACTA SCIENTIARUM-TECHNOLOGY, 2013, 35 (02) : 255 - 262
  • [48] Aging Assessment of Insulating Paper Based on Furfural Concentration Prediction in Transformer Oil
    Zhang, Heng
    Liu, Jiefeng
    Jiang, Zaijun
    Fan, Xianhao
    Zhang, Dongdong
    Li, Wen
    Liu, Chuying
    Rao, Ruidong
    Wu, Thomas
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (04) : 2226 - 2234
  • [49] Analyses of the insulating characteristics of mineral oil at operating conditions
    Eyup Taslak
    Oktay Arikan
    Celal Fadil Kumru
    Ozcan Kalenderli
    Electrical Engineering, 2018, 100 : 321 - 331
  • [50] Analyses of the insulating characteristics of mineral oil at operating conditions
    Taslak, Eyup
    Arikan, Oktay
    Kumru, Celal Fadil
    Kalenderli, Ozcan
    ELECTRICAL ENGINEERING, 2018, 100 (01) : 321 - 331