Study on Degradation Causing Components of Various Characteristics of Transformer Insulating Oil

被引:30
|
作者
Ueta, Genyo [1 ]
Tsuboi, Toshihiro [1 ]
Okabe, Shigemitsu [1 ]
Amimoto, Tsuyoshi [2 ]
机构
[1] Tokyo Elect Power Co Ltd, Tsurumi Ku, Yokohama, Kanagawa 2308510, Japan
[2] Mitsubishi Electr Corp, Ako City, Hyogo 6780256, Japan
关键词
Oil-immersed power transformer; insulating oil; aging; sulfur compound; aging components; alkyl benzene; breakdown voltage; interfacial tension; acidity; dissipation factor; volume resistivity; water content; WATER;
D O I
10.1109/TDEI.2012.6396983
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
To operate power transformers long-term, as well as ensuring their insulating reliability, adequate consideration must also be paid to the age-related decline in various insulating oil characteristics. This decline is considered attributable to the generation and increase of trace components in oil over time, which were not present when the oil was new. In this paper, to identify the components causing such degradation, various components detected in actual field aged transformers were added to the base oil to measure a range of characteristics (water content, acidity, interfacial tension, breakdown voltage, dissipation factor, and volume resistivity). The influence of these additives on various characteristics of insulating oil was evaluated to investigate the components responsible for the decline. When organic acids were added, the acidity value declined, as well as a significant decline in volume resistivity for decanoic acid among organic acids. For methyl ethyl ketone, which is a kind of ketones, a degradation of the characteristics was observed in the dissipation factor and volume resistivity, showing the same trend as that in the investigation results of the actual transformer oil. It emerged that phthalate compounds, or those derived from rubber material among the aromatic series, influenced the dissipation factor and volume resistivity in the presence of water. Consequently, the influence of various components detected in actual transformer oil on various characteristics of insulating oil was clarified.
引用
收藏
页码:2216 / 2224
页数:9
相关论文
共 50 条
  • [21] The Effects of Insulating Oil Replacement Upon Power Transformer Condition Assessment
    Liao, Ruijin
    Lin, Yuandi
    Guo, Pei
    Liu, Haibin
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2015, 43 (17) : 1971 - 1979
  • [22] Transformer Oil Degradation Mechanisms
    Kozlov V.K.
    Valiullina D.M.
    Turanova O.A.
    Turanov N.A.
    Power Technology and Engineering, 2022, 56 (02): : 305 - 308
  • [23] Compatibility of Mineral Insulating Oil with Transformer Construction Materials
    Bernard, Natasa
    Cucek, Biljana
    2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,
  • [24] Aging Effect on Physicochemical Characteristics of Insulating Oil in Service-Aged Transformers
    Fofana, I.
    Hadjadj, Y.
    Amrani, L.
    Bouazabia, S.
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [25] Study on the Insulating Oil Purification System of Ultra-High Voltage(UHV) Transformer
    Cui Liqin
    Xu Shanjun
    Jia Ruiqing
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 3275 - +
  • [26] Degradation level monitoring sensor for insulating oil of power transformer using capacitive high aspect ratio of electrodes
    Kim, S
    Kim, Y
    Yang, J
    Kwon, S
    Park, S
    Transducers '05, Digest of Technical Papers, Vols 1 and 2, 2005, : 613 - 616
  • [27] Experiences with Detection of Transformer Failure Based on Insulating Oil Tests
    Rozga, Pawel
    Piotrowski, Tomasz
    Kozak, Ryszard
    2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,
  • [28] Effects of magnetite and titania nanoparticles on properties of transformer insulating oil
    Pillai, S. Savitha
    Aarathy, A. R.
    Gopinath, Dinesh
    Aryanandiny, B.
    Sankar, Binu
    NANO EXPRESS, 2020, 1 (02):
  • [29] Condition Evaluation of Power Transformer by Analysis of Insulating Oil Tests
    Angkapiyasiri, Montri
    Fuangpian, Phanupong
    Suwanasri, Thanapong
    Suwanasri, Cattareeya
    2018 15TH INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING/ELECTRONICS, COMPUTER, TELECOMMUNICATIONS AND INFORMATION TECHNOLOGY (ECTI-CON), 2018, : 345 - 348
  • [30] Spectroscopic measurement and analysis of water and oil in transformer insulating paper
    Baird, PJ
    Herman, H
    Stevens, GC
    Jarman, PN
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (02) : 293 - 308