An experimental investigation and correlation on buoyant gas temperature below ceiling in a slopping tunnel fire

被引:212
作者
Hu, L. H. [1 ]
Chen, L. F. [1 ]
Wu, L. [1 ]
Li, Y. F. [2 ]
Zhang, J. Y. [3 ]
Meng, N. [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Anhui, Peoples R China
[2] Beijing Univ Technol, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China
[3] China Acad Bldg Res, Beijing 100013, Peoples R China
基金
中国国家自然科学基金;
关键词
Tunnel fire; Slope; Maximum temperature; Temperature decay; Ceiling; LONGITUDINAL VENTILATION SYSTEMS; SMOKE TEMPERATURE; CRITICAL VELOCITY; FLOW;
D O I
10.1016/j.applthermaleng.2012.07.043
中图分类号
O414.1 [热力学];
学科分类号
摘要
The effect of tunnel slope on the fire induced hot gas temperature profile beneath the ceiling has not been clarified nor included in existing models. Thus, in this paper experiments are carried out in a reduced scale model tunnel with dimensions of 6 m (length) x 1.3 m (width) x 0.8 m (height), which is positioned within a 72 m long wind tunnel. The slopes of the model tunnel are varied at three typical different degrees, 0%, 3% and 5%. A LPG porous gas burner is used as fire source. Both the maximum gas temperature and the temperature distribution along the tunnel ceiling are measured and compared with previous models. Results show that those models overestimates the maximum temperature beneath the ceiling of a slopping tunnel fire. The gas temperature decays faster along the ceiling for tunnels with higher slope. Empirical correlations are then proposed to modify the current models to include the tunnel slope factor. The predictions by the modified equations of this work agree well with the measured data in both the maximum temperature and temperature decay beneath the ceiling of the tunnel with different slopes. (c) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:246 / 254
页数:9
相关论文
共 26 条
[1]   Smoke control in sloping tunnels [J].
Atkinson, GT ;
Wu, Y .
FIRE SAFETY JOURNAL, 1996, 27 (04) :335-341
[2]   An experimental study of stratified flow in enclosures [J].
Awad, A. S. ;
Calay, R. K. ;
Badran, O. O. ;
Holdo, A. E. .
APPLIED THERMAL ENGINEERING, 2008, 28 (17-18) :2150-2158
[3]   The influence of longitudinal ventilation systems on fires in tunnels [J].
Carvel, RO ;
Beard, AN ;
Jowitt, PW .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2001, 16 (01) :3-21
[4]   Variation of heat release rate with forced longitudinal ventilation for vehicle fires in tunnels [J].
Carvel, RO ;
Beard, AN ;
Jowitt, PW ;
Drysdale, DD .
FIRE SAFETY JOURNAL, 2001, 36 (06) :569-596
[5]   Simulation of ventilation and fire in the underground facilities [J].
Cheng, LH ;
Ueng, TH ;
Liu, CW .
FIRE SAFETY JOURNAL, 2001, 36 (06) :597-619
[6]  
Cooper L.Y., 1984, P COMBUST I
[7]   THE FLOW OF FIRE GASES UNDER A BEAMED CEILING [J].
DELICHATSIOS, MA .
COMBUSTION AND FLAME, 1981, 43 (01) :1-10
[8]   Fires in tunnels [J].
Grant, GB ;
Jagger, SF ;
Lea, CJ .
PHILOSOPHICAL TRANSACTIONS OF THE ROYAL SOCIETY A-MATHEMATICAL PHYSICAL AND ENGINEERING SCIENCES, 1998, 356 (1748) :2873-2906
[9]  
GRANT GB, 1995, P 5 INT S FIR SAF SC, P1213
[10]   Experimental studies on fire-induced buoyant smoke temperature distribution along tunnel ceiling [J].
Hu, L. H. ;
Huo, R. ;
Wang, H. B. ;
Li, Y. Z. ;
Yang, R. X. .
BUILDING AND ENVIRONMENT, 2007, 42 (11) :3905-3915