Numerical and experimental study on the characteristics of radiant ceiling systems

被引:9
作者
Yuan, Yongli [1 ]
Zhou, Xiang [2 ]
Zhang, Xu [2 ]
机构
[1] Tyndall Natl Inst, Int Energy Res Ctr, Cork, Ireland
[2] Tongji Univ, Sch Mech Engn, Shanghai, Peoples R China
基金
中国国家自然科学基金;
关键词
Radiant system; thermal characteristics; heat flux; surface temperature; operation limit region; COOLING CAPACITY; DISPLACEMENT VENTILATION; THERMAL COMFORT; PERFORMANCE; PANEL; CONDENSATION; HUMIDITY; ENVIRONMENT; CONVECTION; PREDICTION;
D O I
10.1080/09613218.2019.1617668
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Insufficient knowledge about characteristics of radiant systems has caused problems in the wider application of the radiant system, such as water condensation, bad thermal comfort, etc. In this study, key characteristics of a radiant system in terms of an inherent relationship between total heat flux and surface temperature were analysed. General models for describing such the relationship were developed and validated by elaborate experimental data. Operation limit region of the radiant system was identified and proposed by plotting key parameters in one surface, including supply water temperature, operative temperature panel surface temperature as well as total heat flux density. It was found that not all of the points within the operation limit region were suitable for practical application in order to avoid water condensation risk in cooling mode and large temperature differences in a vertical direction in heating mode. Evolved forms of operation limit regions for cooling and heating applications were put forward and their characteristics were addressed. The results reported in this paper could help manufacturers as well as engineers to better design, configure and regulate radiant systems for better product development and improved indoor thermal comfort.
引用
收藏
页码:912 / 927
页数:16
相关论文
共 42 条
[1]   Experimental study on the cooling capacity of a radiant cooled ceiling system [J].
Andres-Chicote, Manuel ;
Tejero-Gonzalez, Ana ;
Velasco-Gomez, Eloy ;
Javier Rey-Martinez, Francisco .
ENERGY AND BUILDINGS, 2012, 54 :207-214
[2]  
[Anonymous], 2005, 157331 EN
[3]  
[Anonymous], 2008, 153771 EN BSI
[4]  
[Anonymous], 2004, 14240 EN
[5]  
ASHRAE, 2003, 138P ASHRAE ASHRAEAN
[6]  
Behne M, 1995, ASHRAE TRAN, V101, P744
[7]   Experimental evaluation of heat transfer coefficients between radiant ceiling and room [J].
Causone, Francesco ;
Corgnati, Stefano P. ;
Filippi, Marco ;
Olesen, Bjarne W. .
ENERGY AND BUILDINGS, 2009, 41 (06) :622-628
[8]   Evaluation of cooling ceiling and mechanical ventilation systems on thermal comfort using CFD study in an office for subtropical region [J].
Chiang, Wei-Hwa ;
Wang, Chia-Ying ;
Huang, Jian-Sheng .
BUILDING AND ENVIRONMENT, 2012, 48 :113-127
[9]   Experimental study and modeling of cooling ceiling systems using steady-state analysis [J].
Diaz, Nestor Fonseca ;
Lebrun, Jean ;
Andre, Philippe .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (04) :793-805
[10]   An experimental study on the performances of a radiation-based task/ambient air conditioning system applied to sleeping environments [J].
Du, Jing ;
Chan, Mingyin ;
Deng, Shiming .
ENERGY AND BUILDINGS, 2017, 139 :291-301