Strategies and operating point optimization of STATCOM control for voltage unbalance mitigation in three-phase three-wire systems

被引:99
作者
Li, Kuang [1 ]
Liu, Jinjun [1 ]
Wang, Zhaoan [1 ]
Wei, Biao [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, Xian 710049, Peoples R China
关键词
control strategy; point of common coupling (PCC); static compensator (STATCOM); voltage-controlled current source (VCCS); voltage-controlled voltage source (VCVS); voltage unbalance;
D O I
10.1109/TPWRD.2006.876655
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Reactive power control through the static compensator (STATCOM) has gained wide attentions due to its outstanding performance. But for a STATCOM with traditional control strategies, unbalanced utility voltages will greatly affect the performance of the STATCOM and, in severe cases, may even cause the shutdown of the STATCOM for overcurrent protection. This paper proposes novel control strategies to ensure normal operation of STATCOM in three-phase three-wire systems when severe system voltage unbalance occurs and, furthermore, to mitigate voltage unbalance at the point of common coupling (PCC) whether it is caused by the utility or load. The control laws, operation principles, compensation characteristics, and operating point optimization of the proposed control strategies are analyzed and compared in detail. The power flow in the STATCOM and corresponding dc-side voltage-control schemes for these control strategies are also introduced. It is shown that the proposed voltage-controlled current source (VCCS) strategy and modified voltage-controlled voltage source strategy are valid for voltage unbalance compensation, especially the VCCS strategy for low rating under the same performance. Finally, the simulation and experimental investigations were carried out with these three parameter-optimized control strategies, respectively, for light and heavy load conditions. The results verified that the current passing through the STATCOM is under control and the voltage at the PCC is more balanced than before compensation. The compensation performance of the STATCOM is thus proven satisfactory.
引用
收藏
页码:413 / 422
页数:10
相关论文
共 19 条
[1]  
Cavaliere CAC, 2002, 2002 IEEE POWER ENGINEERING SOCIETY WINTER MEETING, VOLS 1 AND 2, CONFERENCE PROCEEDINGS, P567, DOI 10.1109/PESW.2002.985066
[2]   REAL-TIME MONITORING OF THE TVA POWER-SYSTEM [J].
CEASE, TW ;
FELDHAUS, B .
IEEE COMPUTER APPLICATIONS IN POWER, 1994, 7 (03) :47-51
[3]   An improved control algorithm of shunt active filter for voltage regulation, harmonic elimination, power-factor correction, and balancing of nonlinear loads [J].
Chandra, A ;
Singh, B ;
Singh, BN ;
Al-Haddad, K .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2000, 15 (03) :495-507
[4]  
CHEN C, 2000, P IEEE POW ENG SOC C, P1258
[5]  
Chen S, 2001, 2001 IEEE POWER ENGINEERING SOCIETY WINTER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-3, P950, DOI 10.1109/PESW.2001.917001
[6]  
de Assis TML, 2002, INT C HARMON QUAL PO, P607
[7]   Harmonic performance analysis of an OPWM-controlled STATCOM in network applications [J].
Filizadeh, S ;
Gole, AM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :1001-1008
[8]  
Hingorani N. G., 1999, UNDERSTANDING FACTS, P10
[9]   Statcom controls for operation with unbalanced voltages [J].
Hochgraf, C ;
Lasseter, RH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (02) :538-544
[10]  
*IEEE, 2000, 14592000 IEEE