Classification of degradation in oil-impregnated cellulose insulation using texture analysis of optical microscopy images

被引:10
作者
Jacob, Nathan D. [1 ,2 ]
Hassanzadeh, Hamid [1 ]
Oliver, Derek R. [1 ]
Sherif, Sherif S. [1 ]
Kordi, Behzad [1 ]
机构
[1] Univ Manitoba, Dept Elect & Comp Engn, 75A Chancellors Circle, Winnipeg, MB R3T 5V6, Canada
[2] Manitoba Hydro, High Voltage Test Facil, 1510 Chevrier Blvd, Winnipeg, MB R3T 1Y6, Canada
关键词
Power transformers; Paper-oil insulation; Life estimation; Microscopy; Image texture analysis; Image classification; POWER TRANSFORMERS;
D O I
10.1016/j.epsr.2015.11.010
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Oil-impregnated Kraft paper samples normally used for power transformer electrical insulation have been artificially aged thermally to produce a sample set with varying levels of insulation deterioration. The samples were aged in an oven at a ternperature above the normal operating temperature of a power transformer. Digital images obtained from optical microscopy measurements on the paper samples have been analyzed using a texture analysis method which converts each image into a spatial gray level dependence matrix (SGLDM). The SGLDM contains information about the statistical variation of pixels gray-level intensities in an image and thereby information about the sample texture. Mathematical operators applied to the SGLDM have been used to extract 22 different statistical texture features for each sample image. Optical microscopy images of the thermally aged samples show that thermal deterioration of the insulation paper produces changes in morphology and physical structure. These changes are detectable by the statistical texture features extracted from the SGLDM texture analysis. Statistical classification is performed on the feature set to demonstrate that differentiation between oil-impregnated paper samples with different levels of thermal degradation is reliable with low error rates. Therefore, development of a practical method to assess condition of oil-impregnated paper insulation using optical microscopy and texture analysis is promising. (C) 2015 Elsevier B.V. All rights reserved.
引用
收藏
页码:104 / 112
页数:9
相关论文
共 28 条
  • [1] [Anonymous], 2009, D564209 ASTM INT STD
  • [2] [Anonymous], 2009, D564299 ASTM, V10.02
  • [3] [Anonymous], 2012, IEEE Guide for Loading Mineral-Oil-Immersed Transformers and Step-Voltage Regulators, IEEE Std C5791-2011 Revis, P1, DOI DOI 10.1109/IEEESTD.2012.6166928
  • [4] [Anonymous], 2007, AGEING CELLULOSE MIN
  • [5] [Anonymous], 2012, ELECT POWER ENG HDB
  • [6] [Anonymous], THESIS U MANCHESTER
  • [7] On-site analysis of transformer paper insulation using portable spectroscopy for chemometric prediction of aged condition
    Baird, Patrick J.
    Herman, Henryk
    Stevens, Gary C.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (04) : 1089 - 1099
  • [8] Non-destructive condition assessment of insulating materials in power transformers
    Baird, PJ
    Herman, H
    Stevens, GC
    [J]. PROCEEDINGS OF THE 2005 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS, VOLS, 1-3, 2005, : 425 - 428
  • [9] Moisture equilibrium in transformer paper-oil systems
    Du, Y
    Zahn, M
    Lesieutre, BC
    Mamishev, AV
    Lindgren, SR
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 1999, 15 (01) : 11 - 20
  • [10] Duda R, 2000, PATTERN CLASSIFICATI