Heat storage efficiency and effective thermal output: Indicators of thermal response and output of radiant heating and cooling systems

被引:37
作者
Krajcik, Michal [1 ]
Sikula, Ondrej [2 ]
机构
[1] Slovak Univ Technol Bratislava, Fac Civil Engn, Radlinskeho 11, Bratislava 81005, Slovakia
[2] Brno Univ Technol, Fac Civil Engn, Veveri 331-95, Brno 60200, Czech Republic
关键词
Radiant heating and cooling; Thermally active building systems (TABS); Thermal response; Response time; Heat storage efficiency; Effective thermal output; Thermal energy stored; MODEL-PREDICTIVE CONTROL; AIR-DISTRIBUTION; PERFORMANCE; FLOOR; VALIDATION; DESIGN;
D O I
10.1016/j.enbuild.2020.110524
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
An alternative indicator of thermal response of radiant heating and cooling systems called heat storage efficiency (HSE) has been tested. The heat storage efficiency was compared with established indicators represented by the time constant tau(63), response time tau(95), and thermal energy stored (TES). The comparison was performed for three wall cooling systems with various combinations of pipe location, configuration of material layers, and materials of the thermal core. Considering the whole response curve (HSE) instead of focusing on one specific point on the curve (tau(63), tau(95)) allowed comparing the thermal response of complex systems by a single value. It also permitted predicting thermal response consistently regardless of the system and core material. Thermal energy stored predicted the thermal response of certain systems, but it may not be suitable for comparing the thermal response of radiant systems with different thermal admittance. Besides, a novel indicator of thermal output called effective thermal output (ETO) has been proposed. The effective thermal output considers both the steady-state thermal performance represented by the nominal thermal output and dynamic thermal performance represented by the heat storage efficiency. For thermally active building systems (TABS), effective thermal output was up to 57% lower than the nominal thermal output. (C) 2020 Elsevier B.V. All rights reserved.
引用
收藏
页数:14
相关论文
共 42 条
[1]  
[Anonymous], 2004, REHVA GUIDEBOOK
[2]  
[Anonymous], 7305481985 STN
[3]  
[Anonymous], 137922012 ISO
[4]  
[Anonymous], 102112008 ISO
[5]   The effect of solar radiation on dynamic thermal performance of floor heating systems [J].
Athienitis, AK ;
Chen, Y .
SOLAR ENERGY, 2000, 69 (03) :229-237
[6]   A METHODOLOGY FOR INTEGRATED BUILDING - HVAC SYSTEM THERMAL-ANALYSIS [J].
ATHIENITIS, AK .
BUILDING AND ENVIRONMENT, 1993, 28 (04) :483-496
[7]   A comparison of heating terminal units: Fan-coil versus radiant floor, and the combination of both [J].
Atienza Marquez, Antonio ;
Cejudo Lopez, Jose Manuel ;
Fernandez Hernandez, Francisco ;
Dominguez Munoz, Fernando ;
Carrillo Andres, Antonio .
ENERGY AND BUILDINGS, 2017, 138 :621-629
[8]  
Babiak J., 2013, Rehva Guidebook, V7, P108
[9]  
Chikh B., 2005, THESIS
[10]  
Etheridge D., 1996, THEORY MEASUREMENT, P724