ON THE EFFECT OF WATER EVAPORATION ON COOLING EFFICIENCY IN COOLING TOWERS

被引:0
作者
Shevelev, Sergey A. [1 ]
Zyablova, Natalia N. [1 ]
机构
[1] Natl Res Tomsk Polytech Univ, 30 Lenin Ave, Tomsk 634050, Russia
来源
BULLETIN OF THE TOMSK POLYTECHNIC UNIVERSITY-GEO ASSETS ENGINEERING | 2019年 / 330卷 / 03期
关键词
Recycling water; heat and mass transfer; cooling tower; water evaporation; convection; DROPLETS; SIMULATION; MOTION;
D O I
10.18799/24131830/2019/3/180
中图分类号
P5 [地质学];
学科分类号
0709 ; 081803 ;
摘要
The paper introduces the results of theoretical study of cooling water droplets as they move in a stream of cold air under conditions characteristic of high-capacity tower cooling towers and the results of a numerical analysis of temperature distributions along the droplet radius. Due to the large temperature differences and significant speeds in the system under consideration, the temperature distribution inside the droplets is assumed to vary along the radius. The increase in air humidity in the near-wall area due to water evaporation is taken into account. The resulting system of nonstationary partial differential equations is solved by the finite difference method using an implicit four-point difference scheme. The solution of the problem with a moving boundary was carried out by the method of catching the front into a node of a spatial grid. To solve nonlinear equations, the iteration method was used. The aim of the work is a numerical evaluation of convective and evaporative cooling contribution to formation of the temperature field of water droplets under conditions typical of modern cooling towers. The analysis was carried out for two characteristic values of the ambient air temperature corresponding to the summer and winter periods of the year. The analysis of the effect of cooling droplets due to water evaporation and thermal conductivity was performed. The temperature distribution over the radius is obtained for different values of the characteristic sizes of droplets. It is shown that the change in radius for the entire range of characteristic sizes of droplets during their flight is less than 0,73 % and does not have a significant effect on the amount of water cooling in the cooling tower. It is established that the absorption of heat by evaporation plays an important role in formation of temperature distribution in the droplets of circulating water at the outlet of the cooling towers. It is shown that at negative ambient temperatures, excessive crushing of droplets is impractical.
引用
收藏
页码:217 / 224
页数:8
相关论文
共 50 条
  • [31] CFD simulation of wet cooling towers
    Al-Waked, R
    Behnia, M
    APPLIED THERMAL ENGINEERING, 2006, 26 (04) : 382 - 395
  • [32] Immersed evaporation and cell inversion: Achieving optimal cooling efficiency for batteries
    Jiang, Xingbao
    Zhang, Dejun
    Wang, Yanan
    Sun, Xin
    Zhang, Yujing
    Xie, Zongfa
    ENERGY, 2025, 320
  • [33] The enhancement of water and energy conservation through condensed water reclamation for evaporative cooling towers
    Leung, Yiu-Kuen
    Cheng, Ka Wai Eric
    FRONTIERS IN WATER, 2024, 6
  • [34] Nozzle arrangement effect on cooling performance of saline water spray cooling
    Sadafi, M. H.
    Jahn, Ingo
    Hooman, Kamel
    APPLIED THERMAL ENGINEERING, 2016, 105 : 1061 - 1066
  • [35] Effect of cold inflow on chimney height of natural draft cooling towers
    Chu, Chi-Ming
    Rahman, Md Mizanur
    Kumaresan, Sivakumar
    NUCLEAR ENGINEERING AND DESIGN, 2012, 249 : 125 - 131
  • [36] Effect Mechanism of Ambient Air Parameters on the Thermal Performance for Cooling Towers
    Zhang, Lei
    Zhou, Jun
    Zuo, Simeng
    An, Guangyao
    Lang, Jinhua
    Yuan, Wei
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2024, 16 (01)
  • [37] WIND TUNNEL SIMULATION OF WIND EFFECT ON A GROUP OF HIGH COOLING TOWERS
    Yan Dachun Li Chenxin (Department of Mechanics
    Acta Mechanica Sinica, 1987, (01) : 36 - 43
  • [38] Suppressed Leidenfrost effect on the rough tool surface with negative skewness for high-efficiency evaporation cooling
    Guo, Yuhang
    Liu, Xiaojun
    Ji, Jiawei
    Wang, Zhaochang
    Hu, Xidong
    Zhu, Yongqing
    Wang, Jiaxiang
    Du, Yu
    Liu, Kun
    Jiao, Yunlong
    APPLIED THERMAL ENGINEERING, 2024, 242
  • [39] Novel method for improving the cooling performance of natural draft wet cooling towers
    Chen, Xuehong
    Sun, Fengzhong
    Chen, Youliang
    Gao, Ming
    APPLIED THERMAL ENGINEERING, 2019, 147 : 562 - 570
  • [40] An equilibrium model for simulating the deposition of calcium carbonate in cooling towers
    da Silva, Amanda F.
    Fernandes, Heloisa L. S.
    Pessoa, Fernando L. P.
    BRAZILIAN JOURNAL OF CHEMICAL ENGINEERING, 2023, 40 (04) : 1133 - 1157