Online Condition Monitoring of MV Switchgear Using D-Dot Sensor to Predict Arc-Faults

被引:38
作者
Hussain, Ghulam Amjad [1 ]
Shafiq, Muhammad [1 ]
Lehtonen, Matti [1 ]
Hashmi, Murtaza [2 ]
机构
[1] Aalto Univ, Sch Elect Engn, FI-00076 Aalto, Finland
[2] Saudi Aramco, Dhahran 31311, Saudi Arabia
关键词
Arc discharge; differential electric field sensor; distribution automation; online condition monitoring; partial discharge; signal de-noising; switchgear; wavelet transform; FIELD PROBE; DISCHARGE;
D O I
10.1109/JSEN.2015.2474122
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
High energy arc faults in medium-voltage (MV) switchgear are serious hazards to personnel or equipment, and may cause process interruptions. Most of the electrical faults leading to arc are developed slowly, e.g., due to insulation degradation or bad connection. In this paper, the detection of partial discharges (PDs) and low energy arcing between loose contacts has been proposed for online monitoring of MV switchgear. The PD measurements in a switchgear panel and arcing measurements across a 0.2-mm sphere-to-rod gap have been carried out. Measured signals are captured by a differential electric field sensor (D-dot sensor) and recorded by a high-frequency oscilloscope. In general, online measured signals are suppressed by high-frequency noise, and therefore, de-noising of measurements is of paramount importance to get reliable information about a fault. An implementation of discrete wavelet transform, to de-noise the measured signals, has been proposed in this paper. Comparison with a well-known infinite impulse response filtering technique has been made. Time and frequency domain comparisons between original and de-noised signals reveal the significance of this technique for arc fault prediction in MV switchgear. A layout for the integration of online monitoring to central control is also presented.
引用
收藏
页码:7262 / 7272
页数:11
相关论文
共 30 条
[11]   Reducing the flash hazard - Methods to protect workers from the devastating effects of arc flash [J].
Dugan, Timothy B. .
IEEE INDUSTRY APPLICATIONS MAGAZINE, 2007, 13 (03) :51-58
[12]   NUMERICAL-ANALYSIS OF OPEN-ENDED CO-AXIAL LINES [J].
GAJDA, GB ;
STUCHLY, SS .
IEEE TRANSACTIONS ON MICROWAVE THEORY AND TECHNIQUES, 1983, 31 (05) :380-384
[13]  
Gao YJ, 1996, IEEE MTT-S, P1537, DOI 10.1109/MWSYM.1996.512229
[14]   Wavelet-based de-noising of on-line PD signals captured by Pearson coil in covered-conductor overhead distribution networks [J].
Hashmi, Murtaza ;
Lehtonen, Matti ;
Nordman, Mikael ;
Jabbar, Rana A. ;
Qureshi, Suhail A. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 43 (01) :1185-1192
[15]   Cross-equipment evaluation of partial discharge measurement and diagnosis techniques in electric power apparatus for transmission and distribution [J].
Hikita, Masayuki ;
Okabe, Shigemitsu ;
Murase, Hiroshi ;
Okubo, Hitoshi .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (02) :505-518
[16]   The Smart Solution for the Prediction of Slowly Developing Electrical Faults in MV Switchgear Using Partial Discharge Measurements [J].
Hussain, G. Amjad ;
Kumpulainen, Lauri ;
Kluss, Joni V. ;
Lehtonen, Matti ;
Kay, John A. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) :2309-2316
[17]   PROTECTING AT THE SPEED OF LIGHT Combining arc-flash sensing and arc-resistant technologies [J].
Kay, John A. ;
Arvola, Juha ;
Kumpulainen, Lauri .
IEEE INDUSTRY APPLICATIONS MAGAZINE, 2011, 17 (03) :12-18
[18]  
Kluss J.V., 2014, P INT C HIGH VOLT EN, P1
[19]  
Kluss J. V., 2011, THESIS
[20]   Empirical analysis of picosecond breakdown in sulfur hexafluoride [J].
Kluss, Joni ;
Hyvonen, Petri .
JOURNAL OF ELECTROSTATICS, 2013, 71 (04) :603-610