A Novel Adaptive Dispersed Phase Current Differential Protection Criterion

被引:0
|
作者
Wang, Chunfeng [1 ]
Lu, Yuping [1 ]
Xiao, Nan [1 ]
Cai, Chao [1 ]
机构
[1] Southeast Univ, Sch Elect Engn, Nanjing 210096, Jiangsu, Peoples R China
关键词
current differential protection; adaptive; through current; line protection; heavy load; transient resistances;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper indicates that the sensitivity of conventional dispersed phase current differential protection criterion using steady currents is impressed by the transient resistances and through currents. A novel adaptive dispersed phase current differential protection criterion is proposed in this paper, and an objective function with the independent variable of fault current component and through current is defined to revise the restraining ratio of differential protection criterion adaptively. The novel criterion possesses higher sensitivity at an internal ground fault with high transient resistances and heavy-loads. It can automatically decrease the restraint coefficients according to the transient resistances and improve the sensitivity at internal faults, while increase them at the external faults adaptively. The comparative analysis of the acting characteristic between the novel and conventional criterion is taken. Simulation results show the feasibility and effectiveness of the novel criterion proposed.
引用
收藏
页数:6
相关论文
共 50 条
  • [21] Sampling value based adaptive differential current protection of transformers
    Hu, Y.
    Chen, D.
    Yin, X.
    Zhang, Z.
    Dianli Xitong Zidonghue/Automation of Electric Power Systems, 2001, 25 (10): : 31 - 34
  • [22] A novel sufficient protection criterion based on adjacent maximal current differences
    Zheng, Jiaqi
    Cao, Chengjie
    Ren, Jiayi
    Sun, Jinghui
    Tian, Fangyuan
    ENERGY REPORTS, 2020, 6 : 1344 - 1348
  • [23] Novel Sensitive Current Differential Protection of Transmission Line
    Dambhare, Sanjay
    Soman, S. A.
    Chandorkar, M. C.
    2008 JOINT INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON) AND IEEE POWER INDIA CONFERENCE, VOLS 1 AND 2, 2008, : 1017 - 1022
  • [24] A novel differential protection method based on simultaneous sampling value of three-phase current
    Sun, BX
    Chan, KW
    Pan, JF
    Conference Record of the 2005 IEEE Industry Applications Conference, Vols 1-4, 2005, : 843 - 847
  • [25] New criterion for line current differential protection by using instantaneous value of fault component
    Gao, Houlei
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2000, 24 (16): : 21 - 24
  • [26] New criterion for current differential protection used for a transmission line with series compensation equipment
    Li Z.
    Bao W.
    Chen Y.
    Weng H.
    Li Z.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (05): : 11 - 19
  • [27] The adaptive unit transverse differential protection based on the fault contributed current
    Tai NengLing
    Wang Bo
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2008, 18 (07): : 742 - 752
  • [28] A new criterion for line current differential protection by using instantaneous value of fault component
    Houlei, Gao
    Dianli Xitong Zidonghue/Automation of Electric Power Systems, 2000, 24 (16):
  • [29] Adaptive compensation scheme of capacitance current to differential protection in UHV lines
    Sang, Bing-Yu
    Wang, Xiao-Ru
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (08): : 1 - 3
  • [30] A Phase Selection Element for Zero Sequence Current Differential Protection
    Wang Xingguo
    Zhou Zexin
    Du Dingxiang
    2014 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2014,