Full-scale multi-ejector module: for a carbon dioxide supermarket refrigeration system: Numerical study of performance evaluation

被引:64
作者
Bodys, Jakub [1 ]
Palacz, Michal [1 ]
Haida, Michal [1 ]
Smolka, Jacek [1 ]
Nowak, Andrzej J. [1 ]
Banasiak, Krzysztof [2 ]
Hafner, Armin [3 ]
机构
[1] Silesian Tech Univ, Inst Thermal Technol, PL-44100 Gliwice, Poland
[2] SINTEF Energy Res, N-7465 Trondheim, Norway
[3] Norwegian Univ Sci & Technol, N-7465 Trondheim, Norway
关键词
CO2; ejector; Fixed ejector; Multi-ejector module; Ejector performance; CO2 refrigeration unit; COP improvement; GEOMETRY EJECTORS; 2-PHASE EJECTOR; COMPUTATIONAL MODEL; R744; EJECTOR; EXPANSION; CYCLE; IMPROVEMENT;
D O I
10.1016/j.enconman.2017.02.007
中图分类号
O414.1 [热力学];
学科分类号
摘要
The performance of fixed ejectors installed in a multi-ejector module in a carbon dioxide refrigeration system is discussed in this paper. To analyse the module operation, three-dimensional ejector models including the inlet and outlet collecting ducts were considered. The tests were performed for three of four vapour ejectors of different sizes that compose the multi-ejector pack. The testing modes included the serial and parallel operation of the fixed units in operating conditions that are characteristic for the supermarket refrigeration unit working at high ambient temperatures. All numerical simulations were performed using the Validated Homogeneous Equilibrium Model implemented on the ejectorPL computational tool for typical transcritical parameters at the motive nozzle port. The detailed analysis was executed separately for the ejectors and the ducts of the module collectors. The results discussion concerned the crucial parameters for such an installation like the pressure and vapour quality distribution. Negligible influence of the motive nozzle collector and a crucial influence of the outlet collector shape was indicated. The global performance analysis showed that the multi-ejector pack provides high and stable performance of all installed ejectors over the entire range of the considered operating conditions for supermarket application. Areas of the possible pressure loss reduction and the uniformity growth in the vapour quality distribution were presented. Finally, according to the multi-ejector pack ducts analysis, the potential areas for module shape optimisation were indicated as well. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:312 / 326
页数:15
相关论文
共 40 条
[1]  
Anderson JD., 1995, Computational Fluid Dynamics
[2]  
Angielczyk W., 2010, P 13 INT REFR AIR CO
[3]  
[Anonymous], 2010, Computational Fluid Dynamics
[4]   Thermodynamics analysis of a modified dual-evaporator CO2 transcritical refrigeration cycle with two-stage ejector [J].
Bai, Tao ;
Yan, Gang ;
Yu, Jianlin .
ENERGY, 2015, 84 :325-335
[5]   Development and performance mapping of a multi-ejector expansion work recovery pack for R744 vapour compression units [J].
Banasiak, Krzysztof ;
Hafner, Armin ;
Kriezi, Ekaterini E. ;
Madsen, Kenneth B. ;
Birkelund, Michael ;
Fredslund, Kristian ;
Olsson, Rickard .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 57 :265-276
[6]   Experimental and numerical investigation of the influence of the two-phase ejector geometry on the performance of the R744 heat pump [J].
Banasiak, Krzysztof ;
Hafner, Armin ;
Andresen, Trond .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (06) :1617-1625
[7]   1D Computational model of a two-phase R744 ejector for expansion work recovery [J].
Banasiak, Krzysztof ;
Hafner, Armin .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2011, 50 (11) :2235-2247
[8]  
Bodys J, 2015, P ECOS 2015 28 INT C
[9]   Performance of fixed geometry ejectors with a swirl motion installed in a multi-ejector module of a CO2 refrigeration system [J].
Bodys, Jakub ;
Smolka, Jacek ;
Palacz, Michal ;
Haida, Michal ;
Banasiak, Krzysztof ;
Nowak, Andrzej J. ;
Hafner, Armin .
ENERGY, 2016, 117 :620-631
[10]   Experimental and computational studies on a steam jet refrigeration system with constant area and variable area ejectors [J].
Chandra, Vineet V. ;
Ahmed, M. R. .
ENERGY CONVERSION AND MANAGEMENT, 2014, 79 :377-386