Comparison of the indoor air quality in an office operating with natural or mechanical ventilation using short-term intensive pollutant monitoring

被引:29
作者
Montgomery, James F. [1 ]
Storey, Stefan [1 ]
Bartlett, Karen [1 ]
机构
[1] Univ British Columbia, Vancouver, BC V6T 1Z4, Canada
关键词
Indoor air quality; Natural ventilation; Hybrid ventilation; HVAC control; Particulate matter; Total volatile organic compounds; PARTICULATE MATTER; OCCUPANT SATISFACTION; CO2; CONCENTRATIONS; THERMAL COMFORT; HEALTH; BUILDINGS; TVOC; FILTRATION; EXPOSURE; COSTS;
D O I
10.1177/1420326X14530999
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Building ventilation systems are used to mitigate occupant exposure to airborne pollutants such as particulate matter (PM), carbon dioxide and total volatile organic compounds. Building rating systems such as Leadership in Energy and Environmental Design promote the use of natural ventilation to reduce building energy consumption while improving occupant satisfaction. A number of investigations have attempted to compare indoor air quality (IAQ) between spaces with natural or mechanical ventilation without reaching a consensus regarding quantitative impacts. This work provides direct quantitative comparison of the IAQ of a single office space designed for operation with either mechanical or natural ventilation. Natural ventilation has been shown to maintain pollutant accumulation below current standards governing IAQ but is subject to significant airflow variability. In contrast, the mechanical ventilation was shown to result in lower levels of indoor pollution and provide tight control of pollutant levels. The correlation between natural ventilation air exchange rate and concentration of total volatile organic compounds was -0.66 compared to no significant correlation for mechanical ventilation. Average indoor to outdoor PM2.5 ratios were found to be 0.87 and 0.5 for natural and mechanical ventilation, respectively. These results show difficulty in controlling indoor pollutants using prescriptive standard ventilation strategies and that performance-based hybrid ventilation systems provide the most flexibility in meeting IAQ needs.
引用
收藏
页码:777 / 787
页数:11
相关论文
共 33 条
  • [1] TVOC and health in non-industrial indoor environments - Report from a Nordic scientific consensus meeting at Langholmen in Stockholm, 1996
    Andersson, K
    Bakke, JV
    Bjorseth, O
    Bornehag, CG
    Clausen, G
    Hongslo, JK
    Kjellman, M
    Kjaergaard, S
    Levy, F
    Molhave, L
    Skerfving, S
    Sundell, J
    [J]. INDOOR AIR, 1997, 7 (02) : 78 - 91
  • [2] [Anonymous], 2009, ASHRAE Handbook|Fundamentals
  • [3] ASHRAE (American Society of Heating Refrigerating and Air-Conditioning Engineers), 2010, 6212010 ANSIASHRAE
  • [4] Is the use of particle air filtration justified? Costs and benefits of filtration with regard to health effects, building cleaning and occupant productivity
    Beko, Gabriel
    Clausen, Geo
    Weschler, Charles J.
    [J]. BUILDING AND ENVIRONMENT, 2008, 43 (10) : 1647 - 1657
  • [5] Berglund B, 1997, 19 EUR COMM
  • [6] Brager G., 2007, Control strategies for mixed-mode buildings
  • [7] Occupant satisfaction in mixed-mode buildings
    Brager, Gail
    Baker, Lindsay
    [J]. BUILDING RESEARCH AND INFORMATION, 2009, 37 (04) : 369 - 380
  • [8] Quantification of indoor TVOC levels from different sources in mechanically ventilated buildings
    Chan, GY
    Chao, CY
    [J]. INDOOR AND BUILT ENVIRONMENT, 2002, 11 (06) : 340 - 350
  • [9] Risk of Non accidental and Cardiovascular Mortality in Relation to Long-term Exposure to Low Concentrations of Fine Particulate Matter: A Canadian National-Level Cohort Study
    Crouse, Dan L.
    Peters, Paul A.
    van Donkelaar, Aaron
    Goldberg, Mark S.
    Villeneuve, Paul J.
    Brion, Orly
    Khan, Saeeda
    Atari, Dominic Odwa
    Jerrett, Michael
    Pope, C. Arden, III
    Brauer, Michael
    Brook, Jeffrey R.
    Martin, Randall V.
    Stieb, David
    Burnett, Richard T.
    [J]. ENVIRONMENTAL HEALTH PERSPECTIVES, 2012, 120 (05) : 708 - 714
  • [10] Relationship between indoor and outdoor levels of fine particle mass, particle number concentrations and black smoke under different ventilation conditions
    Cyrys, J
    Pitz, M
    Bischof, W
    Wichmann, HE
    Heinrich, J
    [J]. JOURNAL OF EXPOSURE ANALYSIS AND ENVIRONMENTAL EPIDEMIOLOGY, 2004, 14 (04): : 275 - 283