Validation tests for the application of a circular PMA with slotted ground plane for partial discharges detection in power transformers

被引:0
作者
Souza, Arthur S. [1 ]
Nobrega, Luiz Augusto M. M. [2 ]
Serres, Alexandre J. R. [2 ]
da Costa, Edson G. [2 ]
Xavier, George V. R. [3 ]
da Cruz, Ana Rita D. [1 ]
Gomes, Matheus Petrcio A. [1 ]
机构
[1] Univ Fed Campina Grande, UFCG, Grad Elect Engn, Campina Grande, Paraiba, Brazil
[2] Univ Fed Campina Grande, DEE UFCG, Elect Engn Dept, Campina Grande, Paraiba, Brazil
[3] Univ Fed Campina Grande, PPgEE UFCG, Postgrad Program Elect Engn PPgEE, Campina Grande, Paraiba, Brazil
来源
2020 14TH EUROPEAN CONFERENCE ON ANTENNAS AND PROPAGATION (EUCAP 2020) | 2020年
关键词
Circular printed monopole antennas; power transformers; partial discharges; slotted ground plane; UHF;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this article, the applicability of an UHF circular printed monopole antenna with slotted ground plane was evaluated in order to detect partial discharges in power transformers. To verify the applicability of the antenna, two measurement batteries were performed: reflection coefficient (bandwidth) and gain in an anechoic chamber, to avoid external interference; and PD sensitivity tests from the comparison with the conventional method of IEC 60270, using for this purpose an oil cell with immersed flat-tip electrodes. These analyzes were performed for the design of an antenna with optimized performance. The obtained values for the antenna's bandwidth, size, gain and PD detection sensitivity make it possible to classify the antenna as efficient in detecting partial discharges in power transformers.
引用
收藏
页数:5
相关论文
共 15 条
[1]  
[Anonymous], 2000, 602702000 IEC
[2]  
[Anonymous], 1964, ELECTR ENG JPN
[3]  
Balanis C., 2007, Antenna Theory: Analysis and Design
[4]  
Chai H., 2018, P 2018 COND MON DIAG, P1
[5]   Application of UHF Sensors in Power System Equipment for Partial Discharge Detection: A Review [J].
Chai, Hua ;
Phung, B. T. ;
Mitchell, Steve .
SENSORS, 2019, 19 (05)
[6]  
Fan Yang, 2016, Progress In Electromagnetics Research C, V69, P105
[7]   DIAGNOSTIC MEASUREMENTS AT UHF IN GAS INSULATED SUBSTATIONS [J].
HAMPTON, BF ;
MEATS, RJ .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1988, 135 (02) :137-144
[8]  
Judd M. D., 1999, Eleventh International Symposium on High Voltage Engineering (Conf. Publ. No.467), P362
[9]   Study on Miniaturized UHF Antennas for Partial Discharge Detection in High-Voltage Electrical Equipment [J].
Liu, Jingcun ;
Zhang, Guogang ;
Dong, Jinlong ;
Wang, Jianhua .
SENSORS, 2015, 15 (11) :29434-29451
[10]   UHF Partial Discharge Location in Power Transformers via Solution of the Maxwell Equations in a Computational Environment [J].
Nobrega, Luiz A. M. M. ;
Costa, Edson G. ;
Serres, Alexandre J. R. ;
Xavier, George V. R. ;
Aquino, Marcus V. D. .
SENSORS, 2019, 19 (15)