Partial Discharge Detection and Induced Surface Current Analysis Using Transient Earth Voltage Method for High Voltage Equipment

被引:0
|
作者
Itose, Akihiko [1 ]
Kozako, Masahiro [1 ]
Hikita, Masayuki [1 ]
机构
[1] Kyushu Inst Technol, Dept Elect & Elect Engn, Kitakyushu, Fukuoka, Japan
来源
2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD) | 2016年
关键词
partial discharge; transient earth voltage (TEV); surface current; finite difference time domain (FDTD); high voltage equipment;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This study deals with advancement of insulation diagnosis technology by partial discharge (PD) detection with transient earth voltage (TEV) signal in high voltage equipment such as oil-filled transformer. TEV detection method allows to detect signals by attaching TEV sensors to the outer wall of the existing facilities. Experiment and analysis of TEV signal propagation using finite-difference time-domain (FDTD) method are carried out for an iron box model which simulates a tank of an actual transformer. Results revealed that TEV signal caused by PD dominantly consists of two kinds of frequency components; i.e. high-frequency component of 500 MHz and low-frequency one of 30 MHz. Namely, the high frequency component of TEV signal propagates from the aperture of the bushing, while the low-frequency component flows through the ground line. Furthermore, it was found that the high-frequency component contained in the TEV signal is attributed to the resonant frequency determined by the size of the metal tank. As a result, if the magnitude and the frequency band of detected TEV signal are known, it is possible to determine where the discharge source is located inside or outside of the metal tank.
引用
收藏
页码:456 / 460
页数:5
相关论文
共 50 条
  • [21] Investigation on propagation mechanism of low frequency component of partial discharge signal measured with transient earth voltage method
    Yoshizumi H.
    Kozako M.
    Hikita M.
    Fujii Y.
    Nakamura Y.
    Cho H.
    IEEJ Transactions on Fundamentals and Materials, 2019, 139 (03) : 154 - 160
  • [22] Condition Assessment of High Voltage Instrument Transformer Using Partial Discharge Analysis
    Talib, Mohd Aizam
    Abu Bakar, Abu Sufian
    Kannan, S. Gobi
    JURNAL TEKNOLOGI, 2013, 64 (04):
  • [23] Partial Discharge Detection Method for High Voltage Converter System Using Wavelet Transform and Convolutional Neural Network
    Kamiya, Tomoki
    Nakamura, Yusuke
    Cho, Hiroaki
    Ishida, Yusuke
    Shiraishi, Hajime
    2022 9TH INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2022, : 207 - 210
  • [24] Partial discharge detection using oscillating voltage at different frequencies
    Morshuis, PHF
    Bodega, R
    Lazzaroni, M
    Wester, FJ
    IMTC 2002: PROCEEDINGS OF THE 19TH IEEE INSTRUMENTATION AND MEASUREMENT TECHNOLOGY CONFERENCE, VOLS 1 & 2, 2002, : 431 - 435
  • [25] Partial Discharge as Threat to Insulation of High Voltage Direct Current Transmissions
    Trotsenko, Yevgeniy
    Brzhezitsky, Volodymyr
    Protsenko, Olexandr
    2019 IEEE 6TH INTERNATIONAL CONFERENCE ON ENERGY SMART SYSTEMS (2019 IEEE ESS), 2019, : 24 - 27
  • [26] Modeling of High-Frequency Current Transformer Based Partial Discharge Detection in High-Voltage Cables
    Hu, Xiao
    Siew, Wah Hoon
    Judd, Martin D.
    Reid, Alistair J.
    Sheng, Bojie
    IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (04) : 1549 - 1556
  • [27] Detection and Analysis of High Voltage Electrical Equipment Corona Discharge Based on Ultraviolet Imaging Technology
    Li Yongxiang
    Wang Tianzheng
    Guo Liqiang
    Wang Zhipeng
    Guo Ting
    Cheng Xueting
    2017 29TH CHINESE CONTROL AND DECISION CONFERENCE (CCDC), 2017, : 6928 - 6931
  • [28] Research on Detection Method for Spatial Discharge of High Voltage Electrical Equipment based on Ultraviolet Monitoring Video
    Luo, Yi
    Wu, Yang
    Hu, Jun
    Duan, Lian
    Chang, Wenzhi
    Bi, Jiangang
    2017 IEEE 5TH INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY (EMC-BEIJING), 2017,
  • [29] Background Noise Level in High Voltage Laboratory Measured by using Partial Discharge Current Sensors
    Daulay, Muhammad Sukri Habibi
    Khayam, Umar
    2017 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND POWER SYSTEMS (ICHVEPS), 2017, : 514 - 518
  • [30] Monitoring of high voltage power transformer using direct optical partial discharge detection technique
    Karmakar, S.
    Roy, N. K.
    Kumbhakar, P.
    JOURNAL OF OPTICS-INDIA, 2009, 38 (04): : 207 - 215