On adapting test function methods for fast detection of fold bifurcations in power systems

被引:8
作者
Hussein, A [1 ]
Chen, K
Wan, HB
机构
[1] Univ Liverpool, Dept Math Sci, Liverpool L69 7ZL, Merseyside, England
[2] Natl Grid Co Plc, Modelling & Anal Grp, Sindlesham RG41 5BN, Berks, England
来源
INTERNATIONAL JOURNAL OF BIFURCATION AND CHAOS | 2002年 / 12卷 / 01期
关键词
D O I
10.1142/S0218127402004255
中图分类号
O1 [数学];
学科分类号
0701 ; 070101 ;
摘要
Test function methods are well known techniques to monitor a continuation method to determine if a fold (saddle-point) bifurcation point has been reached. Two such test functions due to [Abbott, 1978] and [Seydel, 1979] are considered here in a unified framework and their connection to the tangent vector index method from power system community is shown. The challenge in power systems applications is to adapt a test function method to produce a performance index that approximates the fold parameter lambda* without the need of following the solution path to the fold point (x*, lambda*). We demonstrate that the tangent vector index method, due to its connection with the mathematically justifiable test function methods, can lead to a useful performance index.
引用
收藏
页码:179 / 185
页数:7
相关论文
共 28 条
[1]  
ABBOTT JP, 1977, THESIS AUSTR NAT U
[2]  
ABBOTT JP, 1978, J COMPUT APPL MATH, V4, P19, DOI DOI 10.1016/0771-050X(78)90015-3
[3]  
[Anonymous], LECT NOTES NUMERICAL
[4]  
BEYN WJ, 1999, HDB DYNAMICAL SYSTEM, V3
[5]  
Canizares CA, 1996, IEEE T POWER SYST, V11, P1441, DOI 10.1109/59.535685
[6]  
CANIZARES CA, 1999, VOLTAGE STABILITY AS
[7]   An analysis of Seydel's test function methods for nonlinear power flow equations [J].
Chen, K ;
Hussein, A ;
Wan, HB .
INTERNATIONAL JOURNAL OF COMPUTER MATHEMATICS, 2001, 78 (03) :451-470
[8]  
CHEN K, 2001, UNPUB IEEE T POWER S
[9]  
Chiang HD, 1997, IEEE T POWER SYST, V12, P173, DOI 10.1109/59.574937
[10]  
CHIANG HD, 1995, IEEE T POWER SYST, V10, P584, DOI 10.1109/59.387892