An enhanced method for contribution assessment of utility and customer harmonic distortions in radial and weakly meshed distribution systems

被引:26
作者
Farhoodnea, Masoud [1 ]
Mohamed, Azah [1 ]
Shareef, Hussain [1 ]
Zayandehroodi, Hadi [1 ]
机构
[1] Univ Kebangsaan Malaysia, Dept Elect Elect & Syst Engn, Ukm Bangi, Selangor, Malaysia
关键词
Harmonic distortion; Harmonic source location; Power quality; Smart grid; IDENTIFICATION; RESPONSIBILITY;
D O I
10.1016/j.ijepes.2012.05.013
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an enhanced method to assess the share and location of harmonic sources in radial and weakly meshed distribution systems. The proposed method is based on the Norton equivalent circuit in which the measured voltage and current at the point of common coupling (PCC) are used to represent the customer side of the system with its equivalent RLC components. Several case studies have been prepared to validate the accuracy and reliability of the proposed method in order to estimate the share and location of harmonic sources. Simulation results show that the proposed method can accurately solve the problems of harmonic source localization using the minimum knowledge of network parameters. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:222 / 229
页数:8
相关论文
共 24 条
[1]  
[Anonymous], PCFLO USER MANUAL
[2]  
Arrillaga J., 2003, POWER SYSTEM HARMONI
[3]   A New Measurement Method for the Detection of Harmonic Sources in Power Systems Based on the Approach of the IEEE Std. 1459-2000 [J].
Cataliotti, Antonio ;
Cosentino, Valentina .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (01) :332-340
[4]   Critical impedance method - A new detecting harmonic sources method in distribution systems [J].
Chen, CY ;
Liu, XL ;
Koval, D ;
Xu, W ;
Tayjasanant, T .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :288-297
[5]   State Estimation for the Localization of Harmonic Sources in Electric Distribution Systems [J].
D'Antona, Gabriele ;
Muscas, Carlo ;
Sulis, Sara .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2009, 58 (05) :1462-1470
[6]   The sharing of responsibility between the supplier and the consumer for harmonic voltage distortion: A case study [J].
de Paula Silva, Sergio Ferreira ;
de Oliveira, Jose Carlos .
ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (11) :1959-1964
[7]   Identification of harmonic sources of power systems using state estimation [J].
Du, ZP ;
Arrillaga, J ;
Watson, NR ;
Chen, S .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1999, 146 (01) :7-12
[8]  
El Arini MMM, 1998, INT C HARMON QUAL PO, P930, DOI 10.1109/ICHQP.1998.760167
[9]   Harmonic Load Identification Using Complex Independent Component Analysis [J].
Gursoy, Ekrem ;
Niebur, Dagmar .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (01) :285-292
[10]  
Hamzah N., 2004, TENCON 2004. 2004 IEEE Region 10 Conference (IEEE Cat. No. 04CH37582), P220