A modified multi-ground-layer model for borehole ground heat exchangers with an inhomogeneous groundwater flow

被引:84
作者
Lee, C. K. [1 ]
Lam, H. N. [1 ]
机构
[1] Univ Hong Kong, Hong Kong, Hong Kong, Peoples R China
关键词
Ground-source heat pump; Ground heat exchanger; Borehole; Groundwater; Groundwater table; THERMAL RESPONSE TEST; SIMULATION;
D O I
10.1016/j.energy.2012.09.056
中图分类号
O414.1 [热力学];
学科分类号
摘要
A modified model for a borehole ground heat exchanger borefield (BHE) of a ground-source heat pump (GSHP) system was developed based on a three-dimensional finite difference scheme which could cater for multiple ground layers and an inhomogeneous groundwater flow in the soil. The model was validated using FLUENT for a single borehole based on a constant load along the effective length of the borehole with good agreement. The present model was then used to investigate the effect of the groundwater table on the performance of the BHE. It was found that with the borehole partially-submerged in groundwater flow, the borehole specific load along the borehole depth became stratified, the extent of which depended on the various parameter values. The borehole thermal resistance also varied with the relative groundwater table and the groundwater flow velocity. The trends of the fluid temperature leaving a borehole were quite different between the situations when the borehole was partially-submerged in groundwater flow and the case with a full groundwater flow. This meant that the use of an effective groundwater flow velocity to account for the groundwater table effect in a full-groundwater-flow BHE model could be erroneous, particularly for simulation of a large BHE. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:378 / 387
页数:10
相关论文
共 28 条
[1]  
Barcenilla JR, 2005, ASHRAE TRAN, V111, P258
[2]   Ground water level influence on thermal response test in Adana, Turkey [J].
Bozdag, S. ;
Turgut, B. ;
Paksoy, H. ;
Dikici, D. ;
Mazman, M. ;
Evliya, H. .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2008, 32 (07) :629-633
[3]  
Carslaw H.S., 1986, Conduction of Heat In Solids, V2nde
[4]  
Chiasson A.D., 2000, ASHRAE T, V106, P380
[5]   New analytical solution for sizing vertical borehole ground heat exchangers in environments with significant groundwater flow: Parameter estimation from thermal response test data [J].
Chiasson, Andrew ;
O'Connell, Amanda .
HVAC&R RESEARCH, 2011, 17 (06) :1000-1011
[6]  
Claesson J., 2000, P 8 INT C THERM EN S, P195
[7]   Heat transfer in ground heat exchangers with groundwater advection [J].
Diao, NR ;
Li, QY ;
Fang, ZH .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2004, 43 (12) :1203-1211
[8]  
Eskilson P., 1987, Ph.D. Thesis, P264
[9]   A study on the performance of a geothermal heat exchanger under coupled heat conduction and groundwater advection [J].
Fan, Rui ;
Jiang, Yiqiang ;
Yao, Yang ;
Shiming, Deng ;
Ma, Zuiliang .
ENERGY, 2007, 32 (11) :2199-2209
[10]   Review of development from GSHP to UTES in China and other countries [J].
Gao, Qing ;
Li, Ming ;
Yu, Ming ;
Spitler, Jeffrey D. ;
Yan, Y. Y. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2009, 13 (6-7) :1383-1394