Electricity infrastructure vulnerabilities due to long-term growth and extreme heat from climate change in Los Angeles County

被引:38
作者
Burillo, Daniel [1 ]
Chester, Mikhail V. [1 ]
Pincetl, Stephanie [2 ]
Fournier, Eric [2 ]
机构
[1] Arizona State Univ, Dept Civil Environm & Sustainable Engn, 660S Coll Ave, Tempe, AZ 85281 USA
[2] Univ Calif Los Angeles, Inst Environm & Sustainabil, Los Angeles, CA 90024 USA
基金
美国国家科学基金会;
关键词
Electricity infrastructure; Vulnerability assessment; Capacity shortages; Climate change; Extreme heat; Power outages; THERMAL COMFORT; ENERGY-CONSUMPTION; IMPACTS; SYSTEMS; DEMAND; EFFICIENCY; BUILDINGS; ADAPTATION; GENERATION; STATE;
D O I
10.1016/j.enpol.2018.12.053
中图分类号
F [经济];
学科分类号
02 ;
摘要
Many studies have estimated the effects of rising air temperatures due to climate change on electricity infrastructure systems, but none have quantified impacts in terms of potential outages down to the neighborhood scale. Using high-resolution climate projections, infrastructure maps, and forecasts of peak electricity demand for Los Angeles County (LAC), we estimated vulnerabilities in the electricity infrastructure to 2060. We considered rising air temperatures under IPCC RCP 4.5 and RCP 8.5 at 2 km(2) grid cell resolution, two local government population growth scenarios, different efficiency implementations of new residential and commercial buildings, air conditioners (AC), and higher AC penetration. Results were that generators, substations, and transmission lines could lose up to 20% of safe operating capacities (MW). Moreover, based on recent historical load factors for substations in the Southern California Edison service territory, 848-6,724 MW (4-32%) of additional capacity, distributed energy resources, and/or peak load shifting could be needed by 2060 to avoid hardware overloading and outages. If peak load is not mitigated, and/or additional infrastructure capacity not added, then all scenarios result in > 100% substation overloading in Santa Clarita, which would trigger automatic outages, and > 20% substation overloading in at least Lancaster, Palmdale, and Pomona in which protection gear could trip outages within 30 min. Several climate change adaptation options are discussed for electricity infrastructure and building stock with consideration for trade-offs in system stability and other energy and environmental goals.
引用
收藏
页码:943 / 953
页数:11
相关论文
共 94 条
[1]   Vulnerability [J].
Adger, W. Neil .
GLOBAL ENVIRONMENTAL CHANGE-HUMAN AND POLICY DIMENSIONS, 2006, 16 (03) :268-281
[2]  
[Anonymous], 2016, 2016 2040 REG TRANSP
[3]  
[Anonymous], AUG 14 BLACK COMP PR
[4]  
[Anonymous], 2012, AR SO CAL OUT SEPT 8
[5]  
[Anonymous], 2012, IEEE Guide for Loading Mineral-Oil-Immersed Transformers and Step-Voltage Regulators, IEEE Std C5791-2011 Revis, P1, DOI [DOI 10.1109/IEEESTD.2012.6166928, 10.1109/IEEESTD.2012.6166928]
[6]  
[Anonymous], PHOENIX BUS J
[7]  
[Anonymous], BLACK TRACK US ANN R
[8]  
[Anonymous], ENV RES LETT
[9]  
[Anonymous], BUILD EN EFF STAND R
[10]  
[Anonymous], 2016, 2016 - 2040 RTP / SCS Final Growth Forecast by Jurisdiction 2016 - 2040 RTP / SCS Final Growth Forecast by Jurisdiction