Improvement of energy parameters using R442A and R453A in a refrigeration system operating with R404A

被引:32
作者
Oruc, Vedat [1 ]
Devecioglu, Atilla G. [1 ]
Ender, Sertac [1 ]
机构
[1] Dicle Univ, Dept Mech Engn, TR-21280 Diyarbakir, Turkey
关键词
Drop-in; R404A; R442A; R453A; GWP; THERMODYNAMIC PERFORMANCE; COMMERCIAL REFRIGERATION; LOW GWP; R22; ALTERNATIVES; GENERATION;
D O I
10.1016/j.applthermaleng.2017.10.035
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, R404A having high GWP (global warming potential) was experimentally compared with R442A and R453A refrigerants which have low GWP. The alternatives refrigerants of R442A and R453A were directly tested without performing a constructional modification in the refrigeration system. Three different evaporation temperature (-6, -3 and 0 degrees C) and three condenser temperature (35, 40, 45 degrees C) cases were investigated in the experimental work. Power consumption of compressor was highest for R404A while it was the lowest for R453A at three condenser temperatures. The measurements presented that cooling capacity amounts of R442A and R453A were greater by 1-8% than that of R404A. In comparison with R404A, COP (coefficient of performance) value was better by 5-12% using R442A and it was substantially improved by about 10-14% for the case of R453A refrigerant. The volumetric efficiency values were obtained as the highest for R453A at the covered experimental cases. The mass flow rate and quality of refrigerant at evaporator inlet were also reduced as a result of using considered alternatives refrigerants. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:243 / 249
页数:7
相关论文
共 25 条
[1]   Theoretical analysis of a vapour compression refrigeration system with R502, R404A and R507A [J].
Arora, Akhilesh ;
Kaushik, S. C. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (06) :998-1005
[2]   Performance investigation of ozone-friendly R404A and R507 refrigerants as alternatives to R22 in a window air-conditioner [J].
Bolaji, Bukola Olalekan .
ENERGY AND BUILDINGS, 2011, 43 (11) :3139-3143
[3]   Retrofitting of R404a commercial refrigeration systems using R410a and R407f refrigerants [J].
Bortolini, Marco ;
Gamberi, Mauro ;
Gamberini, Rita ;
Graziani, Alessandro ;
Lolli, Francesco ;
Regattieri, Alberto .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2015, 55 :142-152
[4]  
Boscan M., 2015, 51 TEST
[5]   The next generation of refrigerants - Historical review, considerations, and outlook [J].
Calm, James M. .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2008, 31 (07) :1123-1133
[6]   Comparison of a R744 cascade refrigeration system with R404A and R22 conventional systems for supermarkets [J].
da Silva, Alessandro ;
Bandarra Filho, Enio Pedone ;
Pontes Antunes, Arthur Heleno .
APPLIED THERMAL ENGINEERING, 2012, 41 :30-35
[7]  
Devecioglu A. G., 2016, DICLE U MUHENDISLIK, V7, P551
[8]   The influence of plate-type heat exchanger on energy efficiency and environmental effects of the air-conditioners using R453A as a substitute for R22 [J].
Devecioglu, Atilla G. ;
Oruc, Vedat .
APPLIED THERMAL ENGINEERING, 2017, 112 :1364-1372
[9]   Characteristics of Some New Generation Refrigerants with Low GWP [J].
Devecioglu, Atilla Gencer ;
Oruc, Vedat .
CLEAN, EFFICIENT AND AFFORDABLE ENERGY FOR A SUSTAINABLE FUTURE, 2015, 75 :1452-1457
[10]  
DuPont, 2004, THERM PROP DUPONT SU