Wide-Area Traveling Wave Fault Location System Based on IEC61850

被引:57
作者
Chen, Yu [1 ]
Liu, Dong [1 ]
Xu, Bingyin [2 ]
机构
[1] Shanghai Jiao Tong Univ, Sch Elect Informat & Elect Engn, Minist Educ, Key Lab Control Power Transmiss & Convers, Shanghai 200240, Peoples R China
[2] Shandong Univ Technol, Zibo 255049, Peoples R China
关键词
Fault location; IEC61850; traveling wave; wide area;
D O I
10.1109/TSG.2012.2233767
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Existing traveling wave fault location systems employ the double-end method and do not make use of data from neighboring substations. If one of the data acquisition equipments at either end of a line fails to capture the fault transient, no fault location result can be obtained. A wide-area traveling wave fault location (WA-TWFL) system, which makes use of traveling wave data from various substations across the monitored network, is introduced. The WA-TWFL algorithm first identifies the area of the monitored network in which the source of the disturbance originated by analyzing the traveling wave propagation times using the extended double endmethod. Then, the faulty line, and the distance to fault, are determined using selected records from the identified area of the disturbance. This approach provides fault location reliability than the traditional TWFL algorithm. Traveling wave data models based on IEC61850, which supports open communication and interoperability between data acquisition equipment and the master station of the WA-TWFL, are also presented in this paper. The feasibility of the proposed algorithm is proved using traveling wave data from an actual fault on a power grid in China.
引用
收藏
页码:1207 / 1215
页数:9
相关论文
共 15 条
[1]  
[Anonymous], 2003, IEC-61850 Communication Networks and Systems in Substations
[2]  
[Anonymous], 2011, P 2011 IEEE POW EN S
[3]  
Chen N., 2008, NOVEL ALGORITHM TRAV, P1
[4]  
Chen Y., 2010, CHIN INT C 2010 EL D, P1
[5]  
Dong XZ, 2002, 2002 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, VOLS 1-3, CONFERENCE PROCEEDINGS, P1113, DOI 10.1109/PESS.2002.1043442
[6]   Experimental investigations on multi-end fault location system based on current traveling waves [J].
Elhaffar, A. ;
Elkalashy, N. I. ;
Lehtonen, M. .
2007 IEEE LAUSANNE POWERTECH, VOLS 1-5, 2007, :1141-1146
[7]  
Elhaffar A, 2012, IEEE MEDITERR ELECT, P954, DOI 10.1109/MELCON.2012.6196585
[8]  
Feng D., 2008, P 2008 INT C INT COM, P1091
[9]  
Feng D., 2008, RES OPTIMAL PLACEMEN, P573
[10]  
Gale P. F., 1997, Sixth International Conference on Developments in Power System Protection (Conf. Publ. No.434), P192, DOI 10.1049/cp:19970061