A STUDY OF ARC FLASH INCIDENT ENERGY VARIATIONS BASED ON MCC UNIT CONFIGURATION

被引:0
作者
Bugaris, Rachel M. [1 ]
Doan, Daniel R. [2 ]
机构
[1] Rockwell Automat, 1201 South 2nd St, Milwaukee, WI 53204 USA
[2] DuPont Engn, Wilmington, DE 19880 USA
来源
2012 RECORD OF CONFERENCE PAPERS INDUSTRY APPLICATIONS SOCIETY 59TH ANNUAL IEEE PETROLEUM AND CHEMICAL INDUSTRY TECHNICAL CONFERENCE (PCIC) | 2012年
关键词
arc flash; motor control center; incident energy; internal arc fault; unit design; reflectivity;
D O I
暂无
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
There has been significant progress on arc-flash research in recent years, but there has been little focus on how the internal configuration of equipment affects the incident energy released. The relationship between low voltage motor control center (MCC) unit configurations and incident energy exposure resulting from an arc flash is examined in this study. Testing was conducted using actual MCC structures and units. The design of experiment methodology was used to analyze several MCC configuration variables, including unit type, unit size, percent fill of unit, power wire size and length, location of the unit within the structure, and their relationships to incident energy as well as arcing duration and arcing current. The results from 24 arcing tests were analyzed and the magnitude of incident energy measured during the events was observed to be related to the percent fill of components within the units, and properties of interior unit surfaces.
引用
收藏
页数:6
相关论文
共 13 条
[1]  
[Anonymous], 616412008 IECTR
[2]  
[Anonymous], C372072007 IEEE
[3]   INCIDENT ENERGY REDUCTION TECHNIQUES A comparison using low-voltage power circuit breakers [J].
Brown, William A. ;
Shapiro, Ron .
IEEE INDUSTRY APPLICATIONS MAGAZINE, 2009, 15 (03) :53-61
[4]   ARC-RESISTANT EQUIPMENT [J].
Bugaris, Rachel M. ;
Rollay, David T. .
IEEE INDUSTRY APPLICATIONS MAGAZINE, 2011, 17 (04) :62-70
[5]  
Cohen M., 1971, 293 CCL US ARM AB RE
[6]   Protection Planning and System Design to Reduce Arc Flash Incident Energy in a Multi-Voltage-Level Distribution System to 8 cal/cm2 (HRC 2) or Less-Part I: Methodology [J].
Das, J. C. .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2011, 47 (01) :398-407
[7]   Protection Planning and System Design to Reduce Arc-Flash Incident Energy in a Multi-Voltage-Level Distribution System to 8 cal/cm2 (HRC 2) or Less-Part II: Analysis [J].
Das, J. C. .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2011, 47 (01) :408-420
[8]  
Heberlein G. E. Jr., 1996, IEEE Industry Applications Magazine, V2, P35, DOI 10.1109/2943.491384
[9]  
IEEE, IEEE Standard 1584-2002
[10]  
IEEE P1683 Working Group, DEV GUID SPEC MOT CO