Fault-Induced Transient Detection Based on Real-Time Analysis of the Wavelet Coefficient Energy

被引:142
作者
Costa, Flavio B. [1 ]
机构
[1] Univ Fed Rio Grande do Norte, Sch Sci & Technol, BR-59078970 Natal, RN, Brazil
关键词
Fault detection; fault-induced transients; wavelet transform; HARDWARE IMPLEMENTATION; POSITIONAL PROTECTION; TRANSMISSION; CLASSIFICATION; TRANSFORM; SCHEME; RECOGNITION; LOCATION;
D O I
10.1109/TPWRD.2013.2278272
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In the few years, wavelet-based methodologies have been proposed as a good alternative for real-time fault detection. However, these methodologies usually fail to detect faults with overdamped transients and they are highly influenced by the choice of the mother wavelet, presenting time delay in the real-time analysis. By using the discrete wavelet transform (DWT) or the maximal overlap discrete wavelet transform (MODWT), the wavelet coefficient energy has been also used for fault analysis and presents the same drawbacks of the wavelet coefficient analysis. However, this paper presents a novel wavelet-based methodology for real-time detection of fault-induced transients in transmission lines, where the wavelet coefficient energy takes into account the border effects of the sliding windows. As a consequence, the performance of the proposed energy analysis is not affected by the choice of the mother wavelet, presenting no time delay in real-time fault detection, and the fault detection is scarcely influenced to the fault inception angle, fault resistance, and fault location, even if in critical situations where there are no fault-induced transients. The performance of the proposed methodology was assessed by using actual and simulated data. Some records were reproduced to be analyzed in real time with a digital signal processor.
引用
收藏
页码:140 / 153
页数:14
相关论文
共 35 条
[21]   Fast Distance Relay Scheme for Detecting Symmetrical Fault During Power Swing [J].
Pang, Chengzong ;
Kezunovic, Mladen .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2205-2212
[22]   A wavelet-based procedure for automatically determining the beginning and end of transmission system voltage sags [J].
Parsons, AC ;
Grady, WM ;
Powers, EJ .
IEEE POWER ENGINEERING SOCIETY - 1999 WINTER MEETING, VOLS 1 AND 2, 1999, :1310-1315
[23]   Design and hardware implementation of a modular transient directional protection scheme using current signals [J].
Perera, N. ;
Rajapakse, A. D. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2012, 6 (06) :554-562
[24]   Recognition of Fault Transients Using a Probabilistic Neural-Network Classifier [J].
Perera, N. ;
Rajapakse, A. D. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (01) :410-419
[25]   Development and Hardware Implementation of a Fault Transients Recognition System [J].
Perera, Nuwan ;
Rajapakse, Athula D. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (01) :40-52
[26]   High-speed non-unit transmission line protection using single-phase measurements and an adaptive wavelet: zone detection and fault classification [J].
Perez, F. E. ;
Aguilar, R. ;
Orduna, E. ;
Jaeger, J. ;
Guidi, G. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2012, 6 (07) :593-604
[27]  
Probert SA, 2002, 2002 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, VOLS 1-3, CONFERENCE PROCEEDINGS, P801, DOI 10.1109/PESS.2002.1043437
[28]   Hybrid fault diagnosis scheme implementation for power distribution systems automation [J].
Salim, Rodrigo Hartstein ;
de Oliveira, Karen Rezende Caino ;
Filomena, Andre Daros ;
Resener, Mariana ;
Bretas, Arturo Suman .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) :1846-1856
[29]   Power quality assessment via wavelet transform analysis [J].
Santoso, S ;
Powers, EJ ;
Grady, WM ;
Hofmann, P .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) :924-930
[30]   Ultra-high-speed protection of parallel transmission lines using current travelling waves [J].
Sharafi, A. ;
Sanaye-Pasand, M. ;
Jafarian, P. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (06) :656-666