A Saturation Suppression Approach for the Current Transformer-Part I: Fundamental Concepts and Design

被引:27
作者
Davarpanah, Mahdi [1 ]
Sanaye-Pasand, Majid [1 ,2 ]
Iravani, Reza [3 ]
机构
[1] Univ Tehran, Elect & Comp Engn Sch, Coll Engn, Tehran 14395515, Iran
[2] Univ Tehran, Control & Intelligent Proc Ctr Excellence, Elect & Comp Engn Sch, Tehran, Iran
[3] Univ Toronto, Dept Elect & Comp Engn, Toronto, ON M5S 3G4, Canada
关键词
Current transformer (CT); CT desaturation; CT saturation prevention; electronic switch; COMPENSATION; ALGORITHM;
D O I
10.1109/TPWRD.2013.2253496
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The current transformer (CT) is prone to the magnetic core saturation during the power system faults. The CT saturation can prolong and/or miscoordinate operation of relays and thus may result in the system stability problems and equipment damage. This paper proposes a new hardware-based method to suppress or prevent the CT saturation. The proposed approach is based on adding a controllable resistor at the CT secondary circuit which dynamically generates a flux to oppose the time varying flux associated with the decaying dc component of the fault current. Part I of this two-part paper presents the concept, the controllable-switch operational strategy, the design steps, and the parameters of the controllable resistor. Part II provides a comprehensive evaluation of the controllable resistor based on offline digital time-domain simulation and control-hardware-in-the-loop studies.
引用
收藏
页码:1928 / 1935
页数:8
相关论文
共 21 条
[21]   A simple scalar model for magnetic hysteresis [J].
Tellinen, J .