Influences of compressor displacement ratio on dual-loop heat pump system for ventilation heat recovery

被引:6
作者
Wang, Lei [1 ]
Ma, Guoyuan [1 ]
Zhou, Feng [1 ]
机构
[1] Beijing Univ Technol, Coll Environm & Energy Engn, Beijing 100124, Peoples R China
基金
中国国家自然科学基金;
关键词
Heat pump; Dual-loop system; Displacement ratio; Heat recovery; Ventilation; THERMAL PERFORMANCE; PIPE;
D O I
10.1016/j.enbuild.2020.110149
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The performance of heat pump ventilation heat recovery system can be effectively improved using multiple-loop independent compression cycle. The influence of the DR change on the performance of dual-loop system was predicted through calculation to explore the influence of the change in displacement ratio (DR) on the performance of the system and the direction of further improving the performance of the system. The optimum DR in dual-loop system was calculated. The performance differences of two dual-loop heat pump systems with different DR values were compared by experiments. Results show that the optimum DR is between 0.8040 and 0.9206, and this optimum DR maximizes the COP of the system. Experimental results show that, compared with the COP of the system with the DR of 2, that of the system with the DR of 0.5 can be increased by 14.8%. Compared with the overall COP of the triplex loop system with the same displacement in each loop, that of the system with the DR of 0.5 is even higher under certain test conditions. The comparison results of COP changes are in accordance with the prediction of simulation calculation. Therefore, a reasonable increase in the displacement of the low-pressure loop in the multi-loop heat recovery heat pump system will improve the system performance. (c) 2020 Elsevier B.V. All rights reserved.
引用
收藏
页数:11
相关论文
共 27 条
  • [1] Review of heat/energy recovery exchangers for use in ZEBs in cold climate countries
    Alonso, Maria Justo
    Liu, Peng
    Mathisen, Hans M.
    Ge, Gaoming
    Simonson, Carey
    [J]. BUILDING AND ENVIRONMENT, 2015, 84 : 228 - 237
  • [2] [Anonymous], 2017, 51512017 ISO TC
  • [3] Two-stage air-source heat pump for residential heating and cooling applications in northern US climates
    Bertsch, Stefan S.
    Groll, Eckhard A.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (07): : 1282 - 1292
  • [4] A comprehensive review of heat recovery systems for building applications
    Cuce, Pinar Mert
    Riffat, Saffa
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2015, 47 : 665 - 682
  • [5] General Administration of quality Supervision, 2013, MIN ALL VAL EN EFF E
  • [6] General Administration of Quality Supervision Inspection and Quarantine China, 2004, 77252004 GBT GEN ADM
  • [7] Decision-making based on network visualization applied to building life cycle optimization
    Gilles, Fraisse
    Bernard, Souyri
    Ioannis, Axaopoulos
    Simon, Rouchier
    [J]. SUSTAINABLE CITIES AND SOCIETY, 2017, 35 : 565 - 573
  • [8] Theoretical analysis and experimental confirmation of the uniformity principle of temperature difference field in heat exchanger
    Guo, ZY
    Zhou, SQ
    Li, ZX
    Chen, LG
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2002, 45 (10) : 2119 - 2127
  • [9] Energy Performance Certification of Faculty Buildings in Spain: The gap between estimated and real energy consumption
    Herrando, Maria
    Cambra, David
    Navarro, Marcos
    de la Cruz, Lucio
    Milian, Gema
    Zabalza, Ignacio
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 125 : 141 - 153
  • [10] International Organization for Standardization, 2013, 1635822013 ISO, P8