Mechanism Analysis of Particle-Triggered Flashover in Different Gas Dielectrics Under DC Superposition Lightning Impulse Voltage

被引:11
作者
Wang, Jian [1 ]
Wang, Jingrui [1 ]
Hu, Qi [1 ]
Chang, Yanan [1 ]
Liu, Heng [1 ]
Liang, Ruixue [1 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
来源
IEEE ACCESS | 2020年 / 8卷 / 08期
基金
中国国家自然科学基金;
关键词
DC GIL; superimposed voltage; metal particle; C3F7CN/CO2; surface charge; CHARGE ACCUMULATION; FIELD DISTRIBUTION; SURFACE FLASHOVER; SF6; INSULATION; SPACER; AIR; IONIZATION; STRENGTH; MIXTURE;
D O I
10.1109/ACCESS.2020.3026695
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
When DC GIL in operation endures the lightning impulse voltage, the charge accumulation at the gas-solid interface area will seriously affect the insulation performance of the spacer. Considering that gas side conduction is one of the important factors affecting charge accumulation, for the purpose of clarifying of the insulation characteristics of gaseous medium in the flashover process of gas-solid interface, an experimental platform for simulating the working conditions of the spacer is built. The spacer flashover tests were carried out with and without aluminum particle in SF6, 4% C3F7CN /96% CO2 and 20% SF6/80% N-2 gas mixture. The measurement and analysis of surface potential distribution behavior of the spacer was conducted. The experiment results show that the gas dielectric is not the factor which dominate the potential distribution process without aluminum particle, and there is little difference in potential distribution with various gaseous conditions. When the linear aluminum particle appears on the surface of the insulator, it will cause severe electric potential distortion and these potential distorted areas are located around the end of the metal particle near the central conductor, and along with flashover pathway. It has also demonstrated that the gaseous dielectric has influence on the surface charge accumulation behavior especially with metallic particle adhere to spacer surface. Under the C3F7CN/CO2 gas mixture, the surface flashover voltage decrease percentage is about 16.82% and may be lower. Besides, the insulation strength of the gaseous dielectric itself is also a key factor affecting flashover.
引用
收藏
页码:182888 / 182897
页数:10
相关论文
共 30 条
  • [1] Electrical insulation properties of the perfluoronitrile C4F7N
    Chachereau, A.
    Hoesl, A.
    Franck, C. M.
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2018, 51 (49)
  • [2] CHARGING OF INSULATOR SURFACES BY IONIZATION AND TRANSPORT IN GASES
    COOKE, CM
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1982, 17 (02): : 172 - 178
  • [3] Dielectric strength of transformer insulation at DC polarity reversal
    Hasegawa, T
    Yamaji, K
    Hatano, M
    Kouan, T
    Hosokawa, N
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (04) : 1526 - 1531
  • [4] Pulsed townsend measurement of electron transport and ionization in SF6-N2 mixtures
    Hernández-Avila, JL
    de Urquijo, J
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2003, 36 (12) : L51 - L54
  • [5] Iwabuchi H, 2013, IEEE T DIELECT EL IN, V20, P1895, DOI 10.1109/TDEI.2013.6633722
  • [6] Charge distribution measurement on a truncated cone spacer under dc voltage
    Kumada, A
    Okabe, S
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2004, 11 (06) : 929 - 938
  • [7] Novel HVDC Spacers by Adaptively Controlling Surface Charges - Part II: Experiment
    Li, Chuanyang
    Lin, Chuanjie
    Yang, Yong
    Zhang, Bo
    Liu, Weidong
    Li, Qi
    Hu, Jun
    He, Shun
    Liu, Xulei
    He, Jinliang
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (04) : 1248 - 1258
  • [8] Charge accumulation characteristic on polymer insulator surface under AC voltage in air and C4F7N/CO2 mixtures
    Li, Dayu
    Zhang, Guixin
    Wang, Tianyu
    Hou, Yicen
    [J]. HIGH VOLTAGE, 2020, 5 (02): : 160 - 165
  • [9] Flashover Tests on Air Gap of ±800kV DC Transmission Line under Composite DC and Switching Impulse Voltage
    Liao, Yongli
    Li, Ruihai
    Gao, Chao
    Wang, Guoli
    Liu, Zhihong
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (05) : 2095 - 2101
  • [10] Measurement and Simulation of Charge Accumulation on a Disc Spacer with Electro-Thermal Stress in SF6 Gas
    Ma, Guo-ming
    Zhou, Hong-yang
    Liu, Shu-pin
    Wang, Yuan
    Zhao, Shu-jing
    Lu, Shi-jie
    Li, Cheng-rong
    Tu, You-Ping
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (04) : 1221 - 1229