Critical Review of Voltages Applied for Quality-Acceptance and Diagnostic Field Tests on High-Voltage and Extra-High-Voltage Cable Systems

被引:8
|
作者
Hauschild, Wolfgang [1 ,2 ,3 ]
机构
[1] Tech Univ Dresden, D-01062 Dresden, Germany
[2] Damascus Univ, Damascus, Syria
[3] HIGHVOLT Pruftech Dresden GmbH, Dresden, Germany
关键词
high-voltage cable; extra-high-voltage cable; quality-acceptance test; diagnostic field test;
D O I
10.1109/MEI.2013.6457596
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Extruded cable systems are assembled on site. The quality of their components (cable lengths, joints, and terminations) is carefully verified by quality-acceptance tests in the factory (prequalification tests, type tests, and routine tests). These tests are completed by a quality-acceptance test in the field, which verifies the quality of the cable system under service conditions. After the successful commissioning, the cable system is handed over from the supplier to the user. During the decades of operation of the cable system, off-line diagnostic field tests including PD, dielectric measurements, or both are useful for condition assessment of the insulation. The complexity of diagnostic methods demands the application of knowledge rules and has not so stringent requirements to test voltages as qualityacceptance tests. Often the differences between quality-acceptance and diagnostic field tests are not clear. In the following, the suitability of the usual test voltages, applied for extruded cable systems in the field, will be investigated for both, for quality acceptance during commissioning and for condition assessment during operation. The comparison has to consider the remarkable differences of the design field strength of medium-voltage (MV) cables on the one and high-/extra-high-voltage (HV/EHV) cables on the other side. Often no quality-acceptance tests on MV cable systems are performed with separate test-voltage sources, but a great variety of diagnostic off-line tests is applied. The practice of MV cable systems should not simply be transferred to HV/ EHV cable systems. Therefore, this investigation is limited to HV/EHV cable systems, which are of increasing importance for power systems. It has to be mentioned that there is no sharp limit between the MV and HV/EHV range; it shall be assumed in the range of rated voltages between 50 and 72.5 kV. © 2006 IEEE.
引用
收藏
页码:16 / 25
页数:10
相关论文
共 50 条
  • [41] Examination of ageing of the insulation in a new concept of acceptance tests for high-voltage power transformers and apparatus
    Levit, A.G.
    Grechko, O.N.
    Shchipunova, N.P.
    Electrical Technology, 1992, (01):
  • [42] Magnetic-Field Evaluation in the Vicinity of High-Voltage Electric Systems
    Vilacha, C.
    Otero, Antonio F.
    Garrido, C.
    Moreira, J. C.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (02) : 980 - 985
  • [43] Choosing Expert Evaluations of Diagnostic Tests of Electric Insulation for High-Voltage Electric Machines
    Andreev A.M.
    Andreev I.A.
    Lyakhovskii Y.Z.
    Russian Electrical Engineering, 2018, 89 (5) : 318 - 321
  • [44] Novel power quality conditioner applied to high voltage power systems
    Zhang, Changzheng
    Chen, Qiaofu
    Li, Dayi
    Zhao, Youbin
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 2654 - +
  • [45] Thermal field analysis for cable room of high-voltage switchgear and design of online monitoring system
    Xiong, L., 1600, Electric Power Automation Equipment Press (34):
  • [46] Effect of high-voltage electrostatic field on quality of carrot juice during refrigeration
    Hsieh, Chang-Wei
    Ko, Wen-Ching
    LWT-FOOD SCIENCE AND TECHNOLOGY, 2008, 41 (10) : 1752 - 1757
  • [47] Reduction of High-Voltage Cable Line Capacity Caused by Implementation of Magnetic Field Shielding Techniques
    Grinchenko, V
    Tkachenko, O.
    PROBLEMELE ENERGETICII REGIONALE, 2023, (03): : 33 - 41
  • [48] Effects of high-voltage electrostatic field on the freezing behavior and quality of pork tenderloin
    Jia, Guoliang
    He, Xiangli
    Nirasawa, Satoru
    Tatsumi, Eizo
    Liu, Hongjiang
    Liu, Haijie
    JOURNAL OF FOOD ENGINEERING, 2017, 204 : 18 - 26
  • [49] DEVELOPMENT OF EXTRA-HIGH-VOLTAGE SELF-CONTAINED OIL-FILLED CABLE INSULATED WITH NEW SYNTHETIC INSULATING PAPER, ″DCLP″ .
    Fujita, H.
    Itoh, H.
    Ichino, T.
    Nakagawa, M.
    Dainichi-Nippon Densen jiho, 1980, (66): : 1 - 18
  • [50] Influence of the constructive parameters of high-voltage submarine cable lines on the electromagnetic field in a water medium
    Vojtovich, R.A.
    Kadomskaya, K.P.
    Elektrichestvo, 1997, (04): : 15 - 20