Design and control of shunt active power filter for power quality improvement of utility powered brushless DC motor drives

被引:12
作者
Kumaresan, S. [1 ]
Sait, H. Habeebullah [2 ]
机构
[1] Govt Polytech Coll, Dept Elect & Elect Engn, Tuticorin 628008, Tamil Nadu, India
[2] Anna Univ, Univ Coll Engn, Dept Elect & Elect Engn, BIT Campus, Tiruchirappalli, Tamil Nadu, India
关键词
Active filter; BLDC motor; power quality; THD; BLDC MOTOR; CONTROL SCHEME; IMPLEMENTATION;
D O I
10.1080/00051144.2020.1789402
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The presence of nonlinear loads like brushless DC (BLDC) motor drives in the distribution system leads to poor power quality (PQ) indices like low power factor, high total harmonic distortion and creates electromagnetic interference. Passive filters and Power factor correction converters are often inserted between the utility and BLDC motor drives to improve the PQ parameters. This paper proposes the shunt active power filter (SAF) for the PQ improvement of medium and high power BLDC motor drives. In this paper, the design steps and control of an SAF for a 20 kW BLDC motor drive are presented. The control of SAF is realized by applying the instantaneous "p-q" theory with the sinusoidal current control strategy. The current control is realized by a hysteresis controller. In contrast to normal electrical loads, the motor drive loads are subjected to continuous speed and load variations. This will result in fluctuations in the DC-link voltage of the SAF capacitor. Hence, the sliding mode controller is used for DC-link voltage control. The proposed methodology is validated in simulations and the experimental prototype. The enhancement of various PQ parameters is analysed for different loading conditions of the motor in the distorted and non-distorted distribution system voltage conditions.
引用
收藏
页码:507 / 521
页数:15
相关论文
共 28 条
[1]  
Afonso J, 2001, IEEE PORT POWERTECH, P1
[2]  
Akagi H., 2007, IEEE PRESS SERIES PO
[3]   A Hybrid Active Filter for a Three-Phase 12-Pulse Diode Rectifier Used as the Front End of a Medium-Voltage Motor Drive [J].
Akagi, Hirofumi ;
Isozaki, Kohei .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2012, 27 (01) :69-77
[4]   Hardware Implementation of Shunt APF Using Modified Fuzzy Control Algorithm with STM32F407VGT Microcontroller [J].
Anjana, Pradeep ;
Gupta, Vikas ;
Tiwari, Harpal ;
Gupta, Nitin ;
Bansal, Ramesh .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2016, 44 (13) :1530-1542
[5]  
[Anonymous], 1990, 5552 IEC
[6]  
[Anonymous], 2000, 6100032 IEC
[7]  
[Anonymous], 2003, APPL NOTE AN 885 BRU
[8]  
[Anonymous], 519 IEC
[9]  
[Anonymous], 2003, IEEE INT S IND EL
[10]   A Unity Power Factor Bridgeless Isolated Cuk Converter-Fed Brushless DC Motor Drive [J].
Bist, Vashist ;
Singh, Bhim .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (07) :4118-4129