Modeling study of an ejector expansion residential CO2 air conditioning system

被引:35
作者
Liu, Fang [1 ]
Groll, Eckhard A. [1 ]
Li, Daqing [1 ]
机构
[1] Purdue Univ, Sch Mech Engn, Ray W Herrick Labs, W Lafayette, IN 47907 USA
关键词
Energy saving; Ejector efficiencies; CO2 air conditioner model; Two-phase flow; REFRIGERATION CYCLE;
D O I
10.1016/j.enbuild.2012.07.008
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper presents a study of an ejector expansion CO2 air conditioner system. A comprehensive analytical model for 3-ton air-to-air controllable ejector expansion transcritical CO2 air conditioners was developed and validated. The ejector component efficiencies were estimated using empirical correlations, instead of being simply assumed to be fixed values as done in other literature studies. Parametric studies of the ejector expansion CO2 systems show that the coefficient of performance (COP) and the cooling capacity reach maximum levels when the motive nozzle throat diameter becomes 2.8 mm; the maximum cooling COP and cooling capacity occurred for a mixing section constant-area diameter of between 4.1 and 4.2 mm; COP and cooling capacity are affected by the outdoor air temperature. At particular ejector geometries and an outdoor temperature of 37.8 degrees C, the transcritical CO2 system using an ejector as the expansion device outperformed a conventional expansion-valve transcritical CO2 system in COP and cooling capacity by approximately 30.7% and 32.1%. respectively. A careful selection of ejector geometry, such as motive nozzle throat diameter and mixing section constant-area diameter, is critical in order to improve the performance of an ejector expansion CO2 air conditioning system. (C) 2012 Elsevier B.V. All rights reserved.
引用
收藏
页码:127 / 136
页数:10
相关论文
共 15 条
[1]   A verification study of steam-ejector refrigeration model [J].
Alexis, GK ;
Rogdakis, ED .
APPLIED THERMAL ENGINEERING, 2003, 23 (01) :29-36
[2]   Particular characteristics of transcritical CO2 refrigeration cycle with an ejector [J].
Deng, Jian-qiang ;
Jiang, Pei-xue ;
Lu, Tao ;
Lu, Wei .
APPLIED THERMAL ENGINEERING, 2007, 27 (2-3) :381-388
[3]  
Domanski P.A., 1995, P 19 INT C REFR B, P766
[4]   Experimental validation of a prototype ejector designed to reduce throttling losses encountered in transcritical R744 system operation [J].
Elbel, Stefan ;
Hrnjak, Pega .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (03) :411-422
[5]  
ELBEL SW, 2004, P 10 INT REFR AIR CO
[6]  
Jeong J., 2004, P 6 IIR GUST LOR C N
[7]  
Klein S.A., 2019, ENG EQUATION SOLVER
[8]  
Ksayer E.B., 2006, P INT REFR AIR COND
[9]   Transcritical CO2 refrigeration cycle with ejector-expansion device [J].
Li, DQ ;
Groll, EA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (05) :766-773
[10]  
Liu F., 2012, INT J REFRIGERATION