Model predictive control for load frequency of hybrid power system with wind power and thermal power

被引:106
作者
Liu, Jizhen [1 ,2 ]
Yao, Qi [1 ]
Hu, Yang [1 ]
机构
[1] North China Elect Power Univ, Sch Control & Comp Engn, Beijing 102206, Peoples R China
[2] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
基金
中国国家自然科学基金;
关键词
Wind power; Load frequency control; Hybrid power system; Model predictive control; Frequency response model; Gap metric; TURBINE;
D O I
10.1016/j.energy.2019.01.071
中图分类号
O414.1 [热力学];
学科分类号
摘要
With the increase of wind power penetration in generation profile, the contribution of wind power to load frequency control (LFC) has become more significant. To improve the frequency characteristics of a wind-power-contained power system, this paper establishes an analytical linearized model for the frequency response characteristics of wind turbine generator (WTG) during LFC which is helpful to the design of frequency controller. Furthermore, the gap metric measure to the above models under different wind speed ranges is calculated. Under the per unit system, it can be extended as an equivalent model for the whole wind farm. Combining the derived wind farm model and a known thermal power model, an integrated model of hybrid power system can be built. To optimize the frequency-response performance to the power system, an improved LFC method based on model predictive control (MPC) is presented and applied to a multi-areas hybrid system. Then, the wind farms and thermal power plants in the same area can be controlled simultaneously and obtain their reference orders from the predictive controller. The simulation results show that the proposed method can effectively raise the frequency response level of the both power supplies and then improve the frequency performance of power system. (C) 2019 Elsevier Ltd. All rights reserved.
引用
收藏
页码:555 / 565
页数:11
相关论文
共 34 条
[1]   Analysis of frequency sensitive wind plant penetration effect on load frequency control of hybrid power system [J].
Aziz, Asma ;
Oo, Aman Than ;
Stojcevski, Alex .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 99 :603-617
[2]   Robust Frequency Control in an Islanded Microgrid: H∞ and μ-Synthesis Approaches [J].
Bevrani, Hassan ;
Feizi, Mohammad Ramin ;
Ataee, Sirwan .
IEEE TRANSACTIONS ON SMART GRID, 2016, 7 (02) :706-717
[3]  
Cao Jun, 2009, Automation of Electric Power Systems, V33, P78
[4]  
Chengming HE, 2013, AUTOM ELECT POWER SY, V37
[5]   A power control strategy to improve power system stability in the presence of wind farms using FACTS devices and predictive control [J].
Darabian, Mohsen ;
Jalilvand, Abolfazl .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2017, 85 :50-66
[6]   Participation of wind power plants in system frequency control: Review of grid code requirements and control methods [J].
Diaz-Gonzalez, Francisco ;
Hau, Melanie ;
Sumper, Andreas ;
Gomis-Sellmunt, Oriol .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 34 :551-564
[7]   Application of gap metric to model bank determination in multilinear model approach [J].
Du, Jingjing ;
Song, Chunyue ;
Li, Ping .
JOURNAL OF PROCESS CONTROL, 2009, 19 (02) :231-240
[8]  
[付媛 Fu Yuan], 2014, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V34, P4706
[9]  
Georgiou TT., 1988, DECISION CONTROL 198, P1360
[10]  
Gonzalez-Longatt F. M., 2012, 2012 2nd International Symposium on Environment-Friendly Energies and Applications (EFEA 2012), P389, DOI 10.1109/EFEA.2012.6294049