Conduction and breakdown mechanisms in transformer oil

被引:78
作者
Butcher, M [1 ]
Neuber, AA [1 ]
Cevallos, MD [1 ]
Dickens, JC [1 ]
Krompholz, H [1 ]
机构
[1] Texas Tech Univ, Dept Elect Engn, Ctr Pulsed Power & Power Elect, Lubbock, TX 79409 USA
关键词
bubble formation; conduction mechanisms; liquid breakdown; mobility; pressure effects; temperature effects;
D O I
10.1109/TPS.2006.872487
中图分类号
O35 [流体力学]; O53 [等离子体物理学];
学科分类号
070204 ; 080103 ; 080704 ;
摘要
With a fast coaxial test setup using high speed electrical and optical diagnostics, prebreakdown current pulses and shadowgraphy images are measured for direct current (dc) breakdown in Univolt 61 transformer oil. Also, dc currents across the gap are measured using a high sensitivity electrometer. The conduction and breakdown mechanisms in transformer oil as function of applied hydrostatic pressures are quantified. Together, this information provides data on the development of current flow in the system. We have identified three stages in the conduction process prior to breakdown for highly nonuniform fields. Stage 1 is characterized by a resistive current at low fields. Increasing the applied electric field lowers the effective barrier at the metal/dielectric interface allowing a "tunneling" mechanism to begin, leading to the rapid rise in the injection current observed in stage 2. In stage 3, at high fields, the current reaches space charge saturation with an apparent mobility of 3.10(-3) cm(2)/V.s prior to breakdown. The processes of final breakdown show a distinct polarity dependence. A strong pressure dependence of the breakdown voltage is recorded for negative needle/plane breakdown; a 50% reduction in breakdown voltage is observed when the hydrostatic pressure is lowered from atmospheric pressure to hundreds of mtorr. Positive needle discharges show a reduction of only about 10% in breakdown voltage for the reduced pressure case. Weak pressure dependence indicates the breakdown mechanism does not have a strong gaseous component. We will discuss possible links between conduction current and dc breakdown.
引用
收藏
页码:467 / 475
页数:9
相关论文
共 31 条
[1]   SWITCHING AND OTHER NONLINEAR PHENOMENA ASSOCIATED WITH PREBREAKDOWN ELECTRON-EMISSION CURRENTS [J].
ATHWAL, CS ;
LATHAM, RV .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1984, 17 (05) :1029-1043
[2]  
Beroual A, 2002, 2002 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, P248, DOI 10.1109/CEIDP.2002.1048782
[3]  
BUTCHER M, 2003, P 14 IEEE INT PULS P, V1, P289
[4]   COULOMB-DRIVEN CONVECTION IN ELECTROHYDRODYNAMICS [J].
CASTELLANOS, A .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1991, 26 (06) :1201-1215
[5]  
CEVALLOS M, 2003, 14 IEEE INT PULS POW, V2, P1036
[6]  
CHADBAND WG, 1993, 1993 IEEE 11TH INTERNATIONAL CONFERENCE ON CONDUCTION AND BREAKDOWN IN DIELECTRIC LIQUIDS (ICDL), P184, DOI 10.1109/ICDL.1993.593936
[7]  
El-Sulaiman A.A., 1990, IEEE 10 C COND BREAK, P176
[8]   ON THE GASEOUS NATURE OF POSITIVE FILAMENTARY STREAMERS IN HYDROCARBON LIQUIDS .2. PROPAGATION, GROWTH AND COLLAPSE OF GASEOUS FILAMENTS IN PENTANE [J].
GOURNAY, P ;
LESAINT, O .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1994, 27 (10) :2117-2127
[9]   FIELD EMISSION IN LIQUIDS [J].
HALPERN, B ;
GOMER, R .
JOURNAL OF CHEMICAL PHYSICS, 1969, 51 (03) :1031-&
[10]  
Hutchinson I. H., 1987, PRINCIPLES PLASMA DI, P112