Two-Terminal Algorithm Analysis for Unsymmetrical Fault Location on 110 kV Lines

被引:3
作者
Bukvisova, Zuzana [1 ]
Orsagova, Jaroslava [1 ]
Topolanek, David [1 ]
Toman, Petr [1 ]
机构
[1] Brno Univ Technol, Dept Elect Power Engn, Tech 12, Brno 61600, Czech Republic
关键词
unsymmetrical fault location; two-terminal algorithm; sequence components;
D O I
10.3390/en12071193
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This work analyses a two-terminal algorithm designed to locate unsymmetrical faults on 110 kV power transmission lines. The algorithm processes synchronized voltage and current data obtained from both ends of the protected transmission line and calculates the distance of the fault. It is based on decomposing the equivalent circuit into the positive-, negative- and zero-sequence components and finding the point where the output voltages of the right and the left side of the transmission line are equal. Compared to the conventional distance relay locator, the accuracy of this method is higher and less influenced by the fault resistance, the parallel-operated line effect and line asymmetry, as discussed in this work. It is, however, very sensitive to the synchronization accuracy. The mathematical model of the power system was created in the PSCAD (Power Systems Computer Aided Design) environment and the computational algorithm was implemented in Mathematica software.
引用
收藏
页数:14
相关论文
共 18 条
[1]  
[Anonymous], 2013 IEEE POW EN SOC
[2]   Time-time matrix z-score vector-based fault analysis method for series-compensated transmission lines [J].
Asgari Gashteroodkhani, Oveis ;
Vahidi, Behrooz ;
Zaboli, Aydin .
TURKISH JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTER SCIENCES, 2017, 25 (04) :2647-2659
[3]   An iterative two-terminal fault-location method based on unsynchronized phasors [J].
Dalcastagne, Andre Luis ;
Noceti Filho, Sidnei ;
Zuern, Hans Helmut ;
Seara, Rui .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) :2318-2329
[4]   AN ACCURATE FAULT LOCATOR WITH COMPENSATION FOR APPARENT REACTANCE IN THE FAULT RESISTANCE RESULTING FROM REMOTE-END INFEED [J].
ERIKSSON, L ;
SAHA, MM ;
ROCKEFELLER, GD .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (02) :424-436
[5]   A hybrid SVM-TT transform-based method for fault location in hybrid transmission lines with underground cables [J].
Gashteroodkhani, O. A. ;
Majidi, M. ;
Etezadi-Amoli, M. ;
Nematollahi, A. F. ;
Vahidi, B. .
ELECTRIC POWER SYSTEMS RESEARCH, 2019, 170 :205-214
[6]   ACCURATE FAULT LOCATION TECHNIQUE FOR POWER TRANSMISSION-LINES [J].
JOHNS, AT ;
JAMALI, S .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1990, 137 (06) :395-402
[7]   Automated transmission line fault analysis using synchronized sampling at two ends [J].
Kezunovic, M ;
Perunicie, B .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (01) :441-447
[8]   Transmission network fault location observability with minimal PMU placement [J].
Lien, Kai-Ping ;
Liu, Chih-Wen ;
Yu, Chi-Shan ;
Jiang, Joe-Air .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1128-1136
[9]  
MAKWANA H, 2016, ENERGY SYSTEMS IN EL, V17, P40, DOI DOI 10.1007/978-981-10-1572-4
[10]  
Mehala N, 2008, ELE COM ENG, P203