Robustness-Oriented Meter Placement for Distribution System State Estimation in Presence of Network Parameter Uncertainty

被引:62
作者
Pegoraro, Paolo Attilio [1 ,2 ]
Sulis, Sara [1 ]
机构
[1] Univ Cagliari, Dept Elect & Elect Engn, I-09123 Cagliari, Italy
[2] Abbeynet, R&D Grp, Cagliari, Italy
关键词
Distribution system state estimation (DSSE); network parameter uncertainty; optimal meter placement; robustness; weighted least squares (WLS); ALGORITHM; ALLOCATION;
D O I
10.1109/TIM.2013.2243502
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Distribution systems require ad hoc estimators, distribution system state estimation (DSSE) techniques, to acquire knowledge about the system status. An incorrect evaluation of the accuracy of the DSSE creates decision risks in network management. The possible variations in the network parameter values and the decays of the metrological characteristics of the measurement system elements are uncertainty sources very often not considered. Considering these possible lacks of accuracy, this paper focuses on the robustness of distributed measurement systems aimed to obtain accurate DSSE results. The problem of the proper assessment of the accuracy of the DSSE results obtained through a weighted least squares (WLS) approach is faced. A method capable of including different uncertainty sources in the uncertainty estimation of the WLS approach is presented. Furthermore, this paper proposes an optimal meter placement algorithm robust with respect to possible malfunctions in measurement system components. The results obtained on a portion of an Italian distribution network, along with their accuracy, are presented and discussed.
引用
收藏
页码:954 / 962
页数:9
相关论文
共 25 条
[1]   Optimal meter placement for maintaining observability during single branch outages [J].
Abur, A ;
Magnago, FH .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1999, 14 (04) :1273-1278
[2]  
[Anonymous], 2004, Power System State Estimation Theory and Implementation
[3]   STATE ESTIMATION FOR REAL-TIME MONITORING OF DISTRIBUTION-SYSTEMS [J].
BARAN, ME ;
KELLEY, AW .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) :1601-1609
[4]   Meter placement for real-time monitoring of distribution feeders [J].
Baran, ME ;
Zhu, JX ;
Kelley, AW .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (01) :332-337
[5]   A BRANCH-CURRENT-BASED STATE ESTIMATION METHOD FOR DISTRIBUTION-SYSTEMS [J].
BARAN, ME ;
KELLEY, AW .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (01) :483-491
[6]  
Biscaro A. A. P., 2010, 2010 IEEE/PES Transmission & Distribution Conference & Exposition: Latin America (T&D-LA 2010), P37, DOI 10.1109/TDC-LA.2010.5762858
[7]   A multiobjective evolutionary algorithm for the sizing and siting of distributed generation [J].
Celli, G ;
Ghiani, E ;
Mocci, S ;
Pilo, F .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (02) :750-757
[8]   Optimal sectionalizing switches allocation in distribution networks [J].
Celli, G ;
Pilo, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (03) :1167-1172
[9]  
Davoudi M., 2012, P IEEE INT WORKSH AM, P48
[10]  
de Souza J. C. S., 2003, P IEEE BOL POW TECH, V2