Electrical Tree Growth Behavior Under AC and DC High Voltage in Power Cables

被引:0
|
作者
Saleh, Mohammad AlShaikh [1 ,2 ]
Refaat, Shady S. [2 ]
Olesz, Marek [3 ]
Abu-Rub, Haitham [2 ]
机构
[1] Tech Univ Munich, Munich, Germany
[2] Texas A&M Univ, Doha, Qatar
[3] Gdansk Univ Technol, Gdansk, Poland
来源
2021 96TH IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP 2021) / 16TH IEEE NANOTECHNOLOGY MATERIALS AND DEVICES CONFERENCE (IEEE NMDC 2021) | 2021年
关键词
XLPE; power cables; partial discharge; FEA; TRPD; PARTIAL DISCHARGE; INSULATION; INITIATION;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This work investigates the impact of an applied AC and DC high voltage on the electrical tree behavior in extruded cross-linked polyethylene (XLPE) insulation based on simulation and experimental validation. Extensive partial discharge (PD) testing methods are being implemented for high voltage cables under AC voltage for monitoring their condition. However, these PD testing methods cannot be utilized for power cables under DC voltages. DC voltages is considered in this study because of the rising implementation of HVDC cables worldwide. Therefore, it is of paramount importance to study the PD behavior originating from defects under DC voltages. Hence, classifying and diagnosing the defects taking place becomes crucial. In this paper, a 3D finite element analysis (FEA)-based modeling is considered to study the electrical treeing behavior using an embedded needle electrode in the XLPE insulation. The experiment entails PD tests with different applied high DC voltages (2.5, 5, 10, 11, and 12 kV) to study the impact on the initiation of PDs and ultimately tree growth. PD measurements were also investigated under AC voltages (7.1, 9.9, 11.3, 12.7, 14.1, and 17 kV) to compare them with PD results obtained with the applied DC voltage. The time- resolved partial discharge (TRPD) patterns are acquired for classifying the severity of the defect present in the XLPE insulation.
引用
收藏
页码:269 / 274
页数:6
相关论文
共 50 条
  • [31] Influencing Mechanism of Adhesive on Partial Discharge of Pressboard Block under AC/DC Composite Voltage
    Zhang, Yi
    Qi, Bo
    Ma, Yukun
    Huang, Meng
    Yuan, Qing
    Lv, Yuzhen
    Jiao, Yanqiu
    Li, Chengrong
    Zhang, Shuqi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (06) : 1883 - 1891
  • [32] Condition assessment of high voltage power cables
    Gulski, E
    Smit, JJ
    Wester, FJ
    van Doeland, JW
    2004 International Conference on Power System Technology - POWERCON, Vols 1 and 2, 2004, : 1661 - 1666
  • [33] Detection of partial discharges at different AC voltage stresses in power cables
    Wester, Frank. J.
    Gulski, Edward
    Smit, Johan J.
    IEEE ELECTRICAL INSULATION MAGAZINE, 2007, 23 (04) : 28 - 43
  • [34] Insulation Status Assessment in High Voltage Cables Based on Decision Tree Algorithm
    Yazdandoust, A. R.
    Haghjoo, F.
    Shahrtash, S. M.
    2008 IEEE ELECTRICAL POWER AND ENERGY CONFERENCE, 2008, : 127 - +
  • [35] Electrical Tree Characteristics in Polypropylene Under Impulse Superimposed DC Voltage in LN2
    Zhu, Lewei
    Du, Boxue
    Li, Zhonglei
    Su, Jingang
    Jiang, Jinpeng
    Kong, Xiaoxiao
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2019, 29 (02)
  • [36] Partial discharge of oil-paper insulation under DC voltage superimposed AC voltage
    Sun Zhenquan
    Zhao Xuefeng
    Li Jisheng
    Gu Chaomin
    Li Yanming
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (08): : 312 - 318
  • [37] Life and Reliability Models for High Voltage DC Extruded Cables
    Mazzanti, Giovanni
    IEEE ELECTRICAL INSULATION MAGAZINE, 2017, 33 (04) : 42 - 52
  • [38] Electrical Tree Evolution under DC Voltages and Its Differences from AC Trees in Silicone Rubber
    Zhang, Yunxiao
    Zhou, Yuanxiang
    Zhang, Ling
    Teng, Chenyuan
    Zhou, Zhongliu
    Huang, Meng
    2020 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (2020 IEEE CEIDP), 2020, : 176 - 179
  • [39] Surface Charge Coupling Behavior of Fluorinated Polyimide Film under DC and Pulse Voltage
    Du, B. X.
    Li, Jin
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (01) : 567 - 573
  • [40] The Effects of Seasonal Factors on Life and Reliability of High Voltage AC Cables Subjected to Load Cycles
    Mazzanti, Giovanni
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (04) : 2080 - 2088