Detection and Location of Partial Discharges in Power Transformers using Acoustic and Electromagnetic Signals

被引:257
作者
Markalous, Sacha M. [1 ]
Tenbohlen, Stefan [2 ]
Feser, Kurt [2 ]
机构
[1] LDIC GmbH, D-01723 Kesselsdorf, Germany
[2] Univ Stuttgart, Inst Power Transmiss & High Voltage Technol, D-70569 Stuttgart, Germany
关键词
PD location; electromagnetic (UHF) and acoustic PD measurements; de-noising; wavelet; acoustic averaging; arrival time determination;
D O I
10.1109/TDEI.2008.4712660
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The measurement of partial discharges (PD) is a non-destructive and sensitive diagnostic tool for the condition assessment of insulating systems. Two major tasks of PD measurements may be distinguished, (i) PD detection, hence providing evidence and the type of the PD and (ii) the location of the PD. The question "Where is the PD source?" is amongst others tremendously important for scheduling and starting maintenance/repair actions cost and time efficiently or to perform a risk analysis. Here the possibility to geometrically localize the flaw, by means of arrival times of acoustic PD signals, gets an extremely interesting option. Precise acoustic arrival times are consequently essential to accurately locate PD in a power transformer. The averaging of acoustic PD signals helps to enhance the acoustic sensitivity. The acoustic detection limit is lowered significantly and the determination of the arrival times is made possible for weaker PD. Supplementary steps, like automatic objective arrival time determination or additional wavelet-based de-noising further improve the overall location accuracy. A new location approach works with pseudo-times and allows for the use of robust direct solvers instead of the previously used iterative algorithms.
引用
收藏
页码:1576 / 1583
页数:8
相关论文
共 21 条
[1]   AN ALGEBRAIC-SOLUTION OF THE GPS EQUATIONS [J].
BANCROFT, S .
IEEE TRANSACTIONS ON AEROSPACE AND ELECTRONIC SYSTEMS, 1985, 21 (01) :56-59
[2]  
BEYER M, 1987, 5 INT S HV ENG BRAUN, P1
[3]   DE-NOISING BY SOFT-THRESHOLDING [J].
DONOHO, DL .
IEEE TRANSACTIONS ON INFORMATION THEORY, 1995, 41 (03) :613-627
[4]  
Grosse CU, 1999, MATERIALPRUFUNG, V41, P342
[5]  
GROSSMANN E, 2002, THESIS U STUTTGART G
[6]   ULTRASONIC SPECTRUM SIGNATURES OF UNDER-OIL CORONA SOURCES [J].
HARROLD, RT .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1975, 10 (04) :109-112
[7]   LOCATION OF PARTIAL DISCHARGE SITES IN ONLINE TRANSFORMERS [J].
HOWELLS, E ;
NORTON, ET .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (01) :158-162
[8]   PARAMETERS AFFECTING THE VELOCITY OF SOUND IN TRANSFORMER OIL [J].
HOWELLS, E ;
NORTON, ET .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (05) :1111-1115
[9]   DETECTION OF PARTIAL DISCHARGES IN TRANSFORMERS USING ACOUSTIC-EMISSION TECHNIQUES [J].
HOWELLS, E ;
NORTON, ET .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (05) :1538-1549
[10]  
*IEEE, 2003, PC57127D11 IEEE