Study on Coordination of Protective Relays Between Primary Feeder and Interconnecting Transformer Grounded by SFCL of Wind Farm

被引:9
作者
Cho, Sung-Min [1 ]
Shin, Hee-Sang [1 ]
Kim, Jae-Chul [1 ]
机构
[1] Soongsil Univ, Sch Elect Engn, Seoul, South Korea
关键词
Interconnecting transformers; line-to-ground fault; protective relay coordination; superconducting fault current limiter (SFCL);
D O I
10.1109/TASC.2011.2176890
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this study, we analyse the coordination of protective relays between a primary feeder and an interconnecting transformer grounded by using a superconducting fault current limiter (SFCL) of a wind farm. Most wind farms and utility systems are interconnected by a transformer. The winding configuration of most interconnecting transformers is wye grounded-delta. Therefore, the utility-side grounding of the interconnecting transformer can support a new single line-to-ground fault current path. Because the coordination plan of a protective relay in a power distribution system does not consider the new fault path, an unintended relay operation can occur. To overcome this problem, an SFCL is applied to the ground connection of the interconnecting transformer. We analyse the effect of the resistive SFCLs on the coordination of the ground faults using time-domain transient simulation software (PSCAD/EMTDC).
引用
收藏
页数:4
相关论文
共 10 条
  • [1] [Anonymous], POWER SYSTEM ANAL
  • [2] [Anonymous], 15471 IEEE
  • [3] [Anonymous], 2019, C371122018 IEEE
  • [4] [Anonymous], ELECT POWER SYSTEM Q
  • [5] Cho SM, 2010, IEEE POW ENER SOC GE
  • [6] PSCAD/EMTDC-based modeling and analysis of a gearless variable speed wind turbine
    Kim, Seul-Ki
    Kim, Eung-Sang
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (02) : 421 - 430
  • [7] Quench and Recovery Characteristics of a SFCL Applied Into Neutral Line of a Three-Phase Power System
    Lim, Sung-Hun
    Kim, Jin-Seok
    Moon, Jong-Fil
    Kim, Jae-Chul
    Rhee, Sang-Bong
    Kim, Chul-Hwan
    Hyun, Ok-Bae
    [J]. IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2009, 19 (03) : 1835 - 1838
  • [8] Assessment of the Impact of SFCL on Voltage Sags in Power Distribution System
    Moon, Jong-Fil
    Lim, Sung-Hun
    Kim, Jae-Chul
    Yun, Sang-Yun
    [J]. IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2011, 21 (03) : 2161 - 2164
  • [9] The Effect of SFCL on Electric Power Grid With Wind-Turbine Generation System
    Park, Woo-Jae
    Sung, Byung Chul
    Park, Jung-Wook
    [J]. IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2010, 20 (03) : 1177 - 1181
  • [10] Study of Superconducting Fault Current Limiters for System Integration of Wind Farms