A computational model of a transcritical R744 ejector based on a homogeneous real fluid approach

被引:173
作者
Smolka, Jacek [1 ]
Bulinski, Zbigniew [1 ]
Fic, Adam [1 ]
Nowak, Andrzej J. [1 ]
Banasiak, Krzysztof [1 ]
Hafner, Armin [2 ]
机构
[1] Silesian Tech Univ, Inst Thermal Technol, Gliwice, Poland
[2] Sintef Energy Res, Trondheim, Norway
关键词
Two-phase flow; Enthalpy formulation; Real fluid; CO2; Ejector; Heat pump; EXPERIMENTAL VALIDATION; NUMERICAL ASSESSMENT; REFRIGERATION CYCLE; 2-PHASE EJECTORS; CFD ANALYSIS; PERFORMANCE; FLOW; OPERATION; DYNAMICS; SYSTEM;
D O I
10.1016/j.apm.2012.03.044
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
A mathematical model of the compressible transonic single- and two-phase flow of a real fluid is discussed in this paper. The model was originally developed to simulate a refrigerant flow through a heat pump ejector. In the proposed approach, a temperature-based energy equation is replaced with an enthalpy-based formulation, in which the specific enthalpy, instead of the temperature, is an independent variable. A thermodynamic and mechanical equilibrium between gaseous and liquid phases is assumed for the two-phase flow. Consequently, real fluid properties, such as the density, the dynamic viscosity and the diffusion coefficient, are defined as functions of the pressure and the specific enthalpy. The energy equation formulation is implemented in commercial CFD software using subroutines that were developed in-house. The formulations was tested extensively for a single-phase flow of the R141b refrigerant, and for a two-phase flow of the R744 fluid (carbon dioxide) that occurred in a 3-D model of the ejector motive nozzle. In the model validation procedure, a satisfactory comparison between the experimental and computational results of the primary and secondary mass flow rates was obtained for both flow regimes. In addition, in the case of the R744 flow, the pressure distribution along the centre line of the ejector was accurately predicted as well. Furthermore, the results also shows that geometry modelling and measurement accuracy play an important in the final numerical results. As a result of the reasonable computational times, this method can be effectively used for the design of ejectors and also in geometric optimisation computations. (C) 2012 Elsevier Inc. All rights reserved.
引用
收藏
页码:1208 / 1224
页数:17
相关论文
共 31 条
[1]  
Anderson John David, 1995, Computational Fluid Dynamics, V206
[2]  
[Anonymous], 2010, Computational Fluid Dynamics
[3]  
ANSYS, 2009, FLUENT 12 US GUID
[4]   1D Computational model of a two-phase R744 ejector for expansion work recovery [J].
Banasiak, Krzysztof ;
Hafner, Armin .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2011, 50 (11) :2235-2247
[5]   Numerical assessment of ejector operation for refrigeration applications based on CFD [J].
Bartosiewicz, Y ;
Aidoun, Z ;
Mercadier, Y .
APPLIED THERMAL ENGINEERING, 2006, 26 (5-6) :604-612
[6]   Three-dimensional modelling of inductively coupled plasma torches [J].
Bernardi, D ;
Colombo, V ;
Ghedini, E ;
Mentrelli, A .
EUROPEAN PHYSICAL JOURNAL D, 2003, 22 (01) :119-125
[7]   A comparison of heterogenous and homogenous models of two-phase transonic compressible CO2 flow through a heat pump ejector [J].
Bulinski, Zbigniew ;
Smolka, Jacek ;
Fic, Adam ;
Banasiak, Krzysztof ;
Nowak, Andrzej J. .
9TH WORLD CONGRESS ON COMPUTATIONAL MECHANICS AND 4TH ASIAN PACIFIC CONGRESS ON COMPUTATIONAL MECHANICS, 2010, 10
[8]   Computational fluid dynamics (CFD) modelling of local mean age of air distribution in forced-ventilation food plants [J].
Chanteloup, Vivian ;
Mirade, Pierre-Sylvain .
JOURNAL OF FOOD ENGINEERING, 2009, 90 (01) :90-103
[9]   Modelling and optimization of two-phase ejectors for cooling systems [J].
Cizungu, K ;
Groll, M ;
Ling, ZG .
APPLIED THERMAL ENGINEERING, 2005, 25 (13) :1979-1994
[10]  
Colarossi M., 2011, INT J REFRIG