Morphological Lifting Scheme for Current Transformer Saturation Detection and Compensation

被引:49
作者
Lu, Z. [1 ]
Smith, J. S. [1 ]
Wu, Q. H. [1 ]
机构
[1] Univ Liverpool, Dept Elect Engn & Elect, Liverpool L69 3GJ, Merseyside, England
基金
英国工程与自然科学研究理事会;
关键词
Compensation; current transformer; lifting scheme; mathematical morphology; saturation;
D O I
10.1109/TCSI.2008.924112
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Current transformer (CT) saturation can cause protective relay mal-operation or even prevent tripping. The wave shape of the secondary current is severely distorted as the CT is forced into deep saturation when the residual flux in the core adds to the flux change caused by faults. In this paper, a morphological lifting scheme is proposed to extract features contained in the waveform of the signal. The detection of the CT saturation is accurately achieved and the points of the inflection, where the saturation begins and ends, are found with the scheme used. This paper also presents a compensation algorithm, based upon the detection results, to reconstruct healthy secondary currents. The proposed morphological lifting scheme and compensation algorithm are demonstrated on a sample power system. The simulation results clearly indicate that they can successfully detect and compensate the distorted secondary current of a saturated CT with residual flux.
引用
收藏
页码:3349 / 3357
页数:9
相关论文
共 19 条
[1]  
BUNYAGUL T, 2001, P IEEE POW ENG SOC S, P15
[2]  
Cheng N, 2002, MOL CANCER RES, V1, P2
[3]   Lifting construction of non-linear wavelet transforms [J].
Claypoole, RL ;
Baraniuk, RG ;
Nowak, RD .
PROCEEDINGS OF THE IEEE-SP INTERNATIONAL SYMPOSIUM ON TIME-FREQUENCY AND TIME-SCALE ANALYSIS, 1998, :49-52
[4]   Nonlinear wavelet transforms for image coding via lifting [J].
Claypoole, RL ;
Davis, GM ;
Sweldens, W ;
Baraniuk, RG .
IEEE TRANSACTIONS ON IMAGE PROCESSING, 2003, 12 (12) :1449-1459
[5]  
Claypoole RL, 1998, INT CONF ACOUST SPEE, P1513, DOI 10.1109/ICASSP.1998.681737
[6]   An impedance-based CT saturation detection algorithm for bus-bar differential protection [J].
Fernández, C .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (04) :468-472
[7]   Influence of current transformer saturation on line current differential protection algorithms [J].
Gangadharan, P. K. ;
Sidhu, T. S. ;
Klimek, A. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2007, 1 (02) :270-277
[8]   A CT saturation detection algorithm [J].
Kang, YC ;
Ok, SH ;
Kang, SH .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :78-85
[9]   An algorithm for compensating secondary currents of current transformers [J].
Kang, YC ;
Park, JK ;
Kang, SH ;
Johns, AT ;
Aggarwal, RK .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :116-124
[10]   EXPERIMENTAL EVALUATION OF EMTP-BASED CURRENT TRANSFORMER MODELS FOR PROTECTIVE RELAY TRANSIENT STUDY [J].
KEZUNOVIC, M ;
KOJOVIC, L ;
ABUR, A ;
FROMEN, CW ;
SEVCIK, DR ;
PHILLIPS, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (01) :405-412