ARC-FLASH INCIDENT ENERGY REDUCTION USING ZONE SELECTIVE INTERLOCKING

被引:0
作者
Hodgson, Donna Lee [1 ]
Shipp, David [2 ]
机构
[1] Shell Explorat & Prod Co, Specialty Engn Dept, 701 Poydras St, New Orleans, LA 70139 USA
[2] Eaton Elect, Elect Syst & Serv Div, Warrendale, PA 15086 USA
来源
INDUSTRY APPLICATIONS SOCIETY 55TH ANNUAL PETROLEUM AND CHEMICAL INDUSTRY CONFERENCE | 2008年
关键词
Arc-flash; Incident Energy; Electrical Safety; Zone Selective Interlocking; Arc-flash Reduction; Incident Energy Reduction; Low-voltage Switchgear;
D O I
暂无
中图分类号
TE [石油、天然气工业];
学科分类号
0820 ;
摘要
As a result of new requirements in NFPA 70E, many facilities are performing arc-flash hazard analyses to better understand how to protect personnel from the possibility of being injured in an arc-flash incident. In many cases in the petrochemical industry, it is unsafe or not practical to shut down electrical equipment to do work. This paper explores practicable options that a facility has to reduce incident energy levels in existing low-voltage systems where the arc-flash hazard analysis results in unacceptably high levels. It will also explore a case study, in the Gulf of Mexico, where an offshore oil production platform was able to cost effectively reduce incident energy levels from approximately 170 calories/cm(2) to under 15 calories/cm(2) by implementing a zone selective interlocking system into their low-voltage switchgear. The selection process logic involving equipment, personnel considerations and commissioning will all be addressed.
引用
收藏
页码:35 / +
页数:2
相关论文
共 5 条
  • [1] [Anonymous], 2002, 1584 IEEE
  • [2] National Electrical Code, 2019, 70 NFPA
  • [3] *NFPA, 2004, 70E NFPA
  • [4] Electrical safety, arc flash hazards, and "the standards" - A comprehensive overview
    Swencki, SJ
    Smith, JE
    Roybal, DD
    Burns, DB
    Wetzel, GE
    Mohla, DC
    [J]. Industry Applications Society 52nd Annual Petroleum and Chemical Industry Conference, 2005, : 343 - 357
  • [5] Valdes M., 2007, IEEE PCIC