Experimental Study of the Interaction Between Water Sprays and Smoke Layer

被引:7
作者
Blanchard, E. [1 ]
Morlon, R. [1 ,2 ,3 ]
Parent, G. [2 ,3 ]
Fromy, P. [1 ]
Boulet, P. [2 ,3 ]
Borgiallo, D. [4 ]
机构
[1] CSTB, 84 Ave Jean Jaures Champs Marne, F-77447 Marne La Vallee 2, France
[2] Univ Lorraine, LEMTA, UMR 7563, F-54500 Vandoeuvre Les Nancy, France
[3] CNRS, LEMTA, UMR 7563, F-54500 Vandoeuvre Les Nancy, France
[4] PROFOG, Parc Activite Moulin Massy,39 Rue Saule Trapu, F-91300 Massy, France
关键词
Smoke; Water spray; Stratification; Destratification; Opacimetry; Transmission; Visibility; SPRINKLER SPRAY; FIRE SUPPRESSION; MODEL; MIST; STRATIFICATION; DISPLACEMENT;
D O I
10.1007/s10694-017-0693-8
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper concerns the interaction between water sprays and a smoke layer in a corridor, without any interaction with fire activity. Three water sprays are tested, a high-pressure water mist system and two sprinkler systems under different operating pressures. Our study aims to compare the impact of these three sprays on the smoke layer, based on the analysis of temperature and transmittance profiles. Characterization of the smoke layer before spray activation, based on either temperature or transmittance was found to be similar, providing a smoke free layer at around middle height in the corridor. During spray operation, discrepancies were observed in some cases depending on whether the smoke layer was studied based on the temperature or the transmittance profiles. Spray operation may provide gas cooling, resulting in homogeneous temperature profiles, while vertical variations of droplet size and soot or droplet concentration can still induce a variation in transmittance. The impact of water spray on the smoke layer varies with the spray system. For the water mist system and the highest-pressure sprinkler system, the spray operation induces a complete de-stratification with well-mixed steady-state conditions along the corridor as well as strong smoke cooling and visibility alteration. With the lowest-pressure sprinkler system, only a localized alteration of this stratification is observed under the spray, while the environment remains thermally and optically stratified downstream in the corridor despite spray operation. Relationships described in the literature were used to confirm and explain these observations. Ratios were evaluated to compare the drag effect due to the spray and the buoyancy effect related to the fire. All tests provided ratios of drag number over buoyancy number much greater than one. This confirms the ability of these relationships to predict the occurrence of de-stratification. Qualitatively, the highest ratios were found for the high pressure system and for the water mist system, which actually led to the most important de-stratification effects. In contrast, the weaker ratio found for the lower pressure system was still above one, i.e., coherent with a de-stratification which did not affect the whole corridor however.
引用
收藏
页码:479 / 501
页数:23
相关论文
共 25 条
[1]  
[Anonymous], 2008, TECHNICAL REPORT
[2]  
Babrauskas Vytenis., 2002, SFPE HDB FIRE PROTEC, V3rd
[3]   A quasi-steady-state model for predicting fire suppression in spaces protected by water mist systems [J].
Back, GG ;
Beyler, CL ;
Hansen, R .
FIRE SAFETY JOURNAL, 2000, 35 (04) :327-362
[4]   Interaction of sprinklers with smoke and heat vents [J].
Beyler, CL ;
Cooper, LY .
FIRE TECHNOLOGY, 2001, 37 (01) :9-35
[5]   Experimental and Numerical Study of the Interaction Between Water Mist and Fire in an Intermediate Test Tunnel [J].
Blanchard, E. ;
Fromy, P. ;
Carlotti, P. ;
Boulet, P. ;
Desanghere, S. ;
Vantelon, J. P. ;
Garo, J. P. .
FIRE TECHNOLOGY, 2014, 50 (03) :565-587
[6]  
Bullen ML., 1977, Fire Technol, V13, P21, DOI [10.1007/BF02338883, DOI 10.1007/BF02338883]
[7]   WATER MIST AND RADIATION INTERACTIONS: APPLICATION TO A WATER CURTAIN USED AS A RADIATIVE SHIELD [J].
Collin, A. ;
Lechene, S. ;
Boulet, P. ;
Parent, G. .
NUMERICAL HEAT TRANSFER PART A-APPLICATIONS, 2010, 57 (08) :537-553
[8]   AN EXPERIMENTAL-STUDY OF UPPER HOT LAYER STRATIFICATION IN FULL-SCALE MULTI-ROOM FIRE SCENARIOS [J].
COOPER, LY ;
HARKLEROAD, M ;
QUINTIERE, J ;
RINKINEN, W .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1982, 104 (04) :741-749
[9]   Fire suppression by water sprays [J].
Grant, G ;
Brenton, J ;
Drysdale, D .
PROGRESS IN ENERGY AND COMBUSTION SCIENCE, 2000, 26 (02) :79-130
[10]   Determination of interface height from measured parameter profile in enclosure fire experiment [J].
He, YP ;
Fernando, A ;
Luo, MC .
FIRE SAFETY JOURNAL, 1998, 31 (01) :19-38