Influence of Insulation Paper Degradation on Economical Operation Period of Power Transformers

被引:0
|
作者
Cahyono, Bambang [1 ]
Suwarno [2 ]
Hariyanto, Nanang [2 ]
Takahashi, Tsuguhiro [3 ]
Okamoto, Tatsuki [3 ]
机构
[1] Bandung Inst Technol ITB, PT PLN PERSERO, Sch Elect & Informat, Bandung, Indonesia
[2] Bandung Inst Technol ITB, Sch Elect & Informat, Bandung, Indonesia
[3] Ctr Res Inst Elect Power Ind CRIEPI, Elect Power Engn Res Lab, Kanagawa, Japan
关键词
economical operation period; general economical operation period characteristic; specific economical operation period;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Electric utilities have tried to improve their quality of services. At the same time, total expenses should be reduced as much as possible. In this paper, a method to analyze economical operation period of transformers is proposed to solve the problems. There are two approaches performed in this paper, analysis using transformer failure statistics and analysis using transformer operational data. Analysis using transformer failure statistics and population data is carried out as general economical operation period characteristic of the transformers that operate at PLN Java Bali Transmission and Load Dispatch Center. Another analysis using transformer operational data is carried out to give specific economical operation period characteristic of transformer. Four operating conditions with different load and water content are studied to determine economical operation period of transformers for each condition.
引用
收藏
页码:48 / 51
页数:4
相关论文
共 50 条
  • [1] Influence of insulation paper degradation on economical operation period of power transformers
    School of Electrical and Informatics, Bandung Institute of Technology , Jakarta Selatan/Bandung, Indonesia
    不详
    Proc. IEEE Int. Conf. Cond. Monit. Diagn., CMD, (48-51):
  • [2] Thermal Degradation of Cellulose Paper Insulation in Power Transformers
    Mirzaie, M.
    Gholami, A.
    Tayyebi, H.
    2007 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS, VOLS 1 AND 2, 2007, : 673 - +
  • [3] Radiation-chemical degradation of the paper insulation of power transformers
    V. N. Bondareva
    V. B. Komarov
    A. F. Seliverstov
    B. G. Ershov
    M. Yu. L’vov
    S. V. Trifonova
    High Energy Chemistry, 2005, 39 : 196 - 197
  • [4] Radiation-chemical degradation of the paper insulation of power transformers
    Bondareva, VN
    Komarov, VB
    Seliverstov, AF
    Ershov, BG
    L'vov, MY
    Trifonova, SV
    HIGH ENERGY CHEMISTRY, 2005, 39 (03) : 196 - 197
  • [5] Aging Degradation of Insulation Paper in Power Transformers by XRD Method
    Peng, Lei
    Fu, Qiang
    Lin, Musong
    Qian, Yihua
    Lv, Wangyan
    2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [6] Influence of cellulose degradation on insulation life in power transformers
    Emsley, A.M.
    Use of Minerals in Papermaking, 1998, : 115 - 124
  • [7] Moisture Aided Degradation of Oil Impregnated Paper Insulation in Power Transformers
    Mandlik, Manoj
    Ramu, T. S.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (01) : 186 - 193
  • [8] The influence of moisture on the activation energy of the conductivity of paper - oil insulation of power transformers
    Kierczynski, Konrad
    PHOTONICS APPLICATIONS IN ASTRONOMY, COMMUNICATIONS, INDUSTRY, AND HIGH-ENERGY PHYSICS EXPERIMENTS 2016, 2016, 10031
  • [9] Calculation of the Remaining Lifetime of Power Transformers Paper Insulation
    Gorgan, Bogdan
    Notingher, Petru V.
    Wetzer, Jos M.
    Verhaart, Harry F. A.
    Wouters, Peter A. A. F.
    van Schijndel, Arjan
    Tanasescu, Gabriel
    PROCEEDINGS OF THE 13TH INTERNATIONAL CONFERENCE ON OPTIMIZATION OF ELECTRICAL AND ELECTRONIC EQUIPMENT, VOLS 1-5, 2012, : 293 - 300
  • [10] THE KINETICS AND MECHANISMS OF DEGRADATION OF CELLULOSIC INSULATION IN POWER TRANSFORMERS
    EMSLEY, AM
    POLYMER DEGRADATION AND STABILITY, 1994, 44 (03) : 343 - 349