Whole House Particle Removal and Clean Air Delivery Rates for In-Duct and Portable Ventilation Systems

被引:49
|
作者
Macintosh, David L. [1 ]
Myatt, Theodore A. [1 ]
Ludwig, Jerry F. [1 ]
Baker, Brian J. [1 ]
Suh, Helen H. [2 ]
Spengler, John D. [2 ]
机构
[1] Environm Hlth & Engn Inc, Needham, MA 02494 USA
[2] Harvard Univ, Sch Publ Hlth, Boston, MA 02115 USA
关键词
D O I
10.3155/1047-3289.58.11.1474
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
A novel method for determining whole house particle removal and clean air delivery rates attributable to central and portable ventilation/air cleaning systems is described. The method is used to characterize total and air-cleaner-specific particle removal rates during operation of four in-duct air cleaners and two portable air-cleaning devices in a fully instrumented test home. Operation of in-duct and portable air cleaners typically increased particle removal rates over the baseline rates determined in the absence of operating a central fan or an indoor air cleaner. Removal rates of 0.3- to 0.5-mu m particles ranged from 1.5 hr(-1) during operation of an in-duct, 5-in. pleated media filter to 7.2 hr(-1) for an in-duct electrostatic air cleaner in comparison to a baseline rate of 0 hr(-1) when the air handler was operating without a filter. Removal rates for total particulate matter less than 2.5 mu m in aerodynamic diameter (PM2.5) mass concentrations were 0.5 hr(-1) under baseline conditions, 0.5 hr(-1) during operation of three portable ionic air cleaners, 1 hr(-1) for an in-duct 1-in. media filter, 2.4 hr(-1) for a single high-efficiency particle arrestance (HEPA) portable air cleaner, 4.6 hr(-1) for an in-duct 5-in. media filter, 4.7 hr(-1) during operation of five portable HEPA filters, 6.1 hr(-1) for a conventional in-duct electronic air cleaner, and 7.5 hr(-1) for a high efficiency in-duct electrostatic air cleaner. Corresponding whole house clean air delivery rates for PM2.5 attributable to the air cleaner independent of losses within the central ventilation system ranged from 2 m(3)/min for the conventional media filter to 32 m(3)/min for the high efficiency in-duct electrostatic device. Except for the portable ionic air cleaner, the devices considered here increased particle removal indoors over baseline deposition rates.
引用
收藏
页码:1474 / 1482
页数:9
相关论文
共 6 条
  • [1] Measurement of Ozone Emission and Particle Removal Rates from Portable Air Purifiers
    Mang, Stephen A.
    Walser, Maggie L.
    Nizkorodov, Sergey A.
    Laux, John M.
    JOURNAL OF CHEMICAL EDUCATION, 2009, 86 (02) : 219 - 221
  • [2] Particle dispersion and removal associated with kitchen range hood and whole house ventilation system
    Eom, Ye Seul
    Kang, Dong Hwa
    Rim, Donghyun
    Yeo, Myoungsouk
    BUILDING AND ENVIRONMENT, 2023, 230
  • [3] The benefits of whole-house in-duct air cleaning in reducing exposures to fine particulate matter of outdoor origin: A modeling analysis
    MacIntosh, David L.
    Minegishi, Taeko
    Kaufman, Matthew
    Baker, Brian J.
    Allen, Joseph G.
    Levy, Jonathan I.
    Myatt, Theodore A.
    JOURNAL OF EXPOSURE SCIENCE AND ENVIRONMENTAL EPIDEMIOLOGY, 2010, 20 (02) : 213 - 224
  • [4] The benefits of whole-house in-duct air cleaning in reducing exposures to fine particulate matter of outdoor origin: A modeling analysis
    David L MacIntosh
    Taeko Minegishi
    Matthew Kaufman
    Brian J Baker
    Joseph G Allen
    Jonathan I Levy
    Theodore A Myatt
    Journal of Exposure Science & Environmental Epidemiology, 2010, 20 : 213 - 224
  • [5] Evaluation of clean air delivery rates and operating cost effectiveness for room air cleaner and ventilation system in a small lecture room
    Noh, Kwang-Chul
    Yook, Se-Jin
    ENERGY AND BUILDINGS, 2016, 119 : 111 - 118
  • [6] Submicrometer particle removal indoors by a novel electrostatic precipitator with high clean air delivery rate, low ozone emissions, and carbon fiber ionizer
    Kim, H. -J.
    Han, B.
    Kim, Y. -J.
    Oda, T.
    Won, H.
    INDOOR AIR, 2013, 23 (05) : 369 - 378